PDRP-1001 Datasheet, PDF (25/56 Pages) Systemsensor advanced ideas. – Deluge - Preaction Control Panel
Optional Modules
2. Installation
Setup and Configuration
Transmitter Module - 4XTM
Connect a Remote Alarm circuit, Remote Trouble circuit or a Municipal Box to the Transmitter Module
as shown below. Polarities shown in activated positions.
Note: Dummy load terminals 6 and 7 (4.7K, 1/4 W resistor) if Municipal Box is not connected.
Note: Remote Alarm, Remote Trouble and Municipal Box wiring can leave the building.
Pushing the Disconnect Switch down will prevent unwanted activation of the Municipal Box during testing
of the control panel. The Disconnect LED will remain illuminated while the Municipal Box is
disconnected. The System Trouble LED will indicate disconnected and/or Open Circuit conditions on the
Municipal Box.
Cut the TBL Jumper to allow the alarm reverse polarity circuit to open on trouble, if no alarm exists.
The wiring of this module must follow the requirements as specified under "Power-limited Wiring
Requirements" on page 17.
TBL Jumper
Disconnect Switch
TBL
J1
J2
TB1
+
– Remote Alarm (Power-limited)
+ Remote Trouble (Power-limited)
–
No Connection
+
–
Municipal Box (Nonpower-limited)
Disconnect LED
Figure 15 4XTM Configuration
PDRP-1001 Instruction Manual PN 50734:D0 04/06/01