801-2-31-A40 Datasheet, PDF (26/28 Pages) Magnetrol International, Inc. – KotronTM II Series 801 RF Capacitance Transmitter For Level/Flow/Volume
SPECIFICATIONS cont.
AGENCY APPROVALS
Agency Model No.
Approval
801-XX31-N4X Non-hazardous indoor/outdoor
NEMA 4X IP65
Intrinsically Safe Remote
(indoor/outdoor, NEMA 4X IP65
FM*
when installed per Magnetrol
801-XX34-N4X
drawing 99-5043-001
Class I, II & III, Div. 1
Groups A, B, C, D, E, F, & G
NEMA 4X housing mounted in
non-hazardous areas
CAUTION: Agency ratings are based partially on the proper probe
selection. Refer to the chart at the right for approved combinations.
Agency Model No.
801-XX31-N4X
CSA*
801-XX34-N4X
* Approvals pending
Approval
Non-hazardous
indoor/outdoor TYPE 4X
Intrinsically Safe Remote
indoor/outdoor TYPE 4X
when installed per Magnetrol
drawing 99-5043-001
Class I, II & III
Groups A, B, C, D, E, F, & G
Enclosure TYPE 4X mounted
in non-hazardous areas
NOTE: For Groups E & F -
insulated probes must be used.
7th Digit in
Elect. Model No.
1,4
Approved Probes
All probes
INTRINSIC SAFETY
INTRINSIC SAFETY
Models 801-XX34-N4X are pending FM and CSA agency
approval for use as an intrinsically safe circuit.
HAZARDOUS LOCATION
Intrinsically Safe
Class I, II, III, Div. 1,
Groups A, B, C, D, E, F, G
NON-HAZARDOUS LOCATION
Remote Probe
Black
Red
Black
Red
Main Amplifier
Magnetrol Models
880X12--X1XX3X44--NX04XX
8X2-1XX6-G0X
Intrinsic Safety
Ground
Intrinsically Safe/Sécurité Intrinsèque
WARNING: Substitution of components may impair intrinsic
safety.
AVERTISSEMENT: La substitution de composants peut
compomettre la sécurité intrinsèque.
NOTES:
1. The NEC must be followed when installing this equipment.
2. For installation guidance, see ANSI/ISA RP 12.6.
3. The resistance between the associated apparatus intrinsic
safety ground terminal and earth must be less than one ohm.
4. Non-hazardous area equipment connected to the associated
apparatus should not use or generate more than 250 volts.
5. The total cable series inductance and shunt capacitance
between the associated apparatus and the remote probe must
not exceed the indicated values for applicable groups:
Group
AB
CE
DFG
Max. Capacitance
0.13 µF
0.92 µF
2.89 µF
Max. Inductance
0.47 mH
1.97 mH
3.53 mH
26