UNIT CONFIGURATION cont.
SYSTEM CONFIG MENU cont.
Flow and Level Measurement cont.
Press ENT to display current Probe Lo value. Enter the
exact low level of the process medium. Use proper level units
(inches, centimeters, etc.) previously selected. When the
desired value is displayed, press ENT to store the value.
Supr Password? will be displayed if the selection is
changed. Enter your Supr Password at this time. Press ENT
to accept the password and to display Probe Hi.
Move medium to a high point in the tank or simulate level
change by moving the probe. Press ENT to display current
Probe Hi value. Enter the exact level of the process medium.
Use proper level units (inches, centimeters, etc.) previously
selected. When the desired value is displayed, press ENT to
store the value. Supr Password? will be displayed if the
selection is changed. Enter your Supr Password at this
time. Press ENT to accept the password and to display
Previous Menu.
If the application utilizes two probes (dual probe, difference,
or summing) continue to the calibration of Probe 2. Press
ENT to display Probe 2 Select. Press ENT to display Level
Units and begin calibration of Probe 2. Enter all values for
Level Units, Mode Setup, Level Limit, Probe Lo, and Probe
Hi points.
System Configuration is now complete. Proceed to I/O
Configuration on Page 20 to continue Unit Configuration.
Remote rigid probe
Parshall
Flume
Stilling Well