UNIT CONFIGURATION cont.
SYSTEM CONFIG MENU cont.
Level Measurement cont.
Press ENT to display current Probe Lo value. Enter the
exact low level of the process medium. Use proper level units
(inches, centimeters, etc.) previously selected. When the
desired value is displayed, press ENT to store the value.
Supr Password? will be displayed if the selection is
changed. Enter your Supr Password at this time. Press ENT
to accept the password and to display Probe Hi Point.
Move medium to a high point in the tank or simulate the level
change by moving the probe. Press ENT to display current
Probe Hi value. Enter the exact level of the process medium.
Use proper level units (inches, centimeters, etc.) previously
selected. When the desired value is displayed, press ENT to
store the value. Supr Password? will be displayed if the
selection is changed. Enter your Supr Password at this
time. Press ENT to accept the password and to display
Previous Menu.
If the application utilizes two probes (dual probe, difference,
or summing) continue to the calibration of Probe 2. Press
ENT to display Probe 2 Select. Press ENT to display Level
Units and begin calibration of Probe 2. Enter all values for
Level Units, Mode Setup, Probe Lo, and Probe Hi points.
System Configuration is now complete. Proceed to I/O
Configuration on Page 20 to continue Unit Configuration.
Probe Hi
Probe Lo
13