UNIT CONFIGURATION cont.
SYSTEM CONFIG MENU cont.
Flow and Level Measurement
This menu is used to configure the main control parameters
of the Series 801 for flow and level measurements.
For the purposes of this manual and to become familiar with
the configuration parameters of this unit, all instructions will
be shown. It is important to note that once in the System
Config menu, you may scroll through the selections by using
the UP or DOWN arrow. Once the desired selection is dis-
played, press ENT. The unit is capable of being configured in
three different modes of operation.
• Level Only
• Volume & Level
• Flow & Level
The menu layout for Flow and Level Measurement is
shown below.
Series 801
Measured Values
System Config - Flow and Level
Measurement
Unit Operation
Level Units
Mode Setup
Flow Element
Flow Units
Low Flow Cutoff
Level Limit
Probe Lo Point
Probe Hi Point
Previous Menu
Please refer to the above menu layout for the configura-
tion instructions below.
From the Default Display, press ENT to view the Measured
Values menu. Press DOWN arrow to display System
Config.
Press ENT once again to enter the System Config menu and
to display Unit Operation. Press ENT to display the present
configuration. Use the UP or DOWN arrow to scroll through
the options. When the desired selection is displayed, press
ENT to store the value. If the mode selection has changed, a
warning will appear:
***WARNING*** This mode change WILL erase ALL set-
tings! Confirm change by pressing <9> will be displayed
if the selection has been changed. Press <9> to confirm.
Supr Password? will be displayed and your chosen pass-
word must be entered at this time. The unit will display the
next menu item
SYSTEM CONFIG MENU cont
Level Units
Inches
Feet
Centimeters
Meters
Please refer to the above menu layout for the configura-
tion instructions below.
Press ENT once again to enter System Config and to display
Level Units. Press ENT to display the present units of mea-
surement. Use the UP or DOWN arrow to scroll through units
of measurement. When the desired selection is displayed,
press ENT to store the value. Password? will be displayed if
the selection has been changed and your chosen password
must be entered at this time. The unit will display the next
menu item – Mode Setup.
Mode Set Up
Level Only
Volume & Level
Flow & Level
With Mode Set Up displayed, press ENT to display the
present mode. Scroll UP or DOWN until the desired mode is
displayed. Press ENT. If the mode selection has been
changed, a warning will appear:
***WARNING*** This mode change WILL erase ALL set-
tings! Confirm change by pressing <9> will be displayed
if the selection has been changed. Press <9> to confirm.
Supr Password? will be displayed and your chosen pass-
word must be entered at this time. The unit will display the
next menu item - Flow Element.
Flow and Level
Flow Element
V-notch 22.5°
30°
45°
60°
90°
120°
Parshall 1"
2"
3"
6"
9"
12"
18"
24"
36"
48"
60"
72"
96"
120"
144"