801-2-31-A40 Datasheet, PDF (16/28 Pages) Magnetrol International, Inc. – KotronTM II Series 801 RF Capacitance Transmitter For Level/Flow/Volume
UNIT CONFIGURATION cont.
SYSTEM CONFIG MENU cont.
Custom Table
If a custom table is selected, Password? will be displayed.
Enter password and Table Name will be displayed. Press
ENT and the present name will appear on the display. Press
the 2nd key to start the left value/letter scrolling. If a faster
scrolling speed is desired, press 2nd again. Make the selec-
tion by pressing ENT to lock in the first letter/value designa-
tion of the Table name. Press ENT once again to proceed to
the next character. Perform the same steps as stated above.
When completed, press ENT and the display will read Max.
Table Span. Enter the maximum span in the units of mea-
surement selected. Max. Table Value will then be displayed.
Enter the maximum value in the customer conversion/strap-
ping table. Table Units will be displayed. Enter via the 2nd
key in any units. Press ENT and display reads ENTER
TABLE PTS. Press ENT again to read 00%: Begin entering
percent of volume for each % of height displayed in 2%
steps. Table is complete after all 51 points are entered. After
entering the points in the table, Previous Menu is displayed.
Press ENT to continue to Volume Units.
Password? will be displayed and your chosen password
must be entered at this time. Press ENT to acknowledge the
accepted password and the unit will display the next menu
item – Volume Units.
Volume Units
Cubic Feet
Gallons
Million Gallons
Cubic Meters
Liters
Million Liters
Petroleum Barrel
With Volume Units displayed, press ENT to display the
selected units. Scroll to the desired Volume Units and press
ENT. If the mode selection has changed, a warning will
appear:
***WARNING*** This mode change WILL erase ALL set-
tings! Confirm change by pressing <9> will be displayed
if the selection has been changed. Press <9> to confirm.
Supr Password? will be displayed and your chosen pass-
word must be entered at this time. The unit will display the
next menu item – Level Limit.
Press ENT to display the maximum level possible in the pre-
sent units of measurement. Press ENT to display the next
menu item – Probe Lo.
Refer to Page 7 on selection of a General or Supervisory
Password.
SYSTEM CONFIG MENU cont.
NOTES:
1. The Probe Lo and Probe Hi points are the most critical
entries in the calibration procedure. Be sure of the val-
ues before they are entered.
2. The media level must be moved to accomplish this pro-
cedure. The Probe Lo and Probe Hi points can be
entered in any order and can be easily changed in the
future when the process level is at a much higher or
lower point.
3. A minimum level change of two percent (2%) of tank
height (or 5pF, whichever is greater) will yield a valid
calibration. However, a large change yields better
accuracy.
4. The unit will automatically "time out" and revert back to
the Default Display after four minutes if without a key-
stroke. Any information already entered will remain in
memory. Simply reenter the System Config. section and
enter any remaining data.
Press ENT to display current Probe Lo value. Enter the
exact low level of the process medium. Use proper level units
(inches, centimeters, etc.) previously selected. When the
desired value is displayed, press ENT to store the value.
Supr Password? will be displayed if the selection is
changed. Enter your Supr Password at this time. Press ENT
to accept the password and to display Probe Hi.
Move medium to a high point in the tank or simulate the level
change by moving the probe.Press ENT to display current
Probe Hi value. Enter the exact level of the process medium.
Use proper level units (inches, centimeters, etc.) previously
selected. When the desired value is displayed, press ENT to
store the value. Supr Password? will be displayed if the
selection is changed. Enter your Supr Password at this
time. Press ENT to accept the password and to display
Previous Menu.
If the application utilizes two probes (dual probe, difference,
or summing) continue to the calibration of Probe 2. Press
ENT to display Probe 2 Select. Press ENT to display Level
Units and begin calibration of Probe 2. Enter all values for
Level Units, Mode Setup, Probe Lo, and Probe Hi points.
System Configuration is now complete. Proceed to I/O
Configuration on Page 20 to continue Unit Configuration.
16