English
Language : 

801-2-31-A40 Datasheet, PDF (22/28 Pages) Magnetrol International, Inc. – KotronTM II Series 801 RF Capacitance Transmitter For Level/Flow/Volume
UNIT CONFIGURATION cont.
CALIBRATION MENU
This menu is used to calibrate non-control parameters of the
Series 801. Each menu item will prompt for Sup Pswd? as a
protection against unauthorized changes.
Series 801
Measured Values
System Config
I/O Config
Advanced Configuration
Damping
Set Clock
Enter Tag
Default Display
Calculation
Change Password
Change Sup Pass
Previous Menu
Damping
This allows for smoothing of the 4–20 mA output signal to
achieve a stable display and output under turbulent level
conditions. Values of 0 to 50 are available. Increasing the
value will increase the damping and slow the response. The
factory setting of 10 should be utilized until an unstable dis-
play or output is observed.
Set Clock
This allows for changing of the date and time on the smart-
watch option. Unit prompts for:
Month?
Date?
Year?
Hour?
Minute?
After entering these values, in military format, the unit
prompts ENTer to set and then asks for the supervisory
password.
Enter Tag
This menu shows the present tag - Magnetrol 801. (If utiliz-
ing multiple probes, Probe 1 Select will be displayed. A tag
may be entered for each probe).
If desired, this tag can be changed by using the UP or DOWN
arrows to scan through characters and press ENT to change
the character at that location in the tag. Pressing the 2nd key
will start the scrolling of the available characters. Press ENT
when the desired character is shown.
CALIBRATION MENU cont.
Default Display
This menu allows for a choice of items displayed during nor-
mal operation. The following items may be toggled
ENABLED/DISABLED using the UP and DOWN arrow:
Probe 1 Tag
P1 Level
P1 Vol/Flow
Probe 2 Tag
P2 Level
P2 Vol/Flow
Comb. Level
Comb. Vol/Flow
Loop
Clock
Calculation
Totalizer
Previous Menu
The last menu item is Previous Menu. If any change was
made in the default display, ENT at this point will cause the
unit to prompt for the Sup Pswd.
Calculation
Press ENT to display Existing Test Is. Press ENT again to
display Text: ___ . Enter text by using UP or DOWN arrow
keys, pressing the 2nd key and pressing ENT at each entry.
The display will then read MULT:. This is the multiplier used
in the calculation. Your level, flow or volume reading is mul-
tiplied by this value.
NOTE: The calculation is only for display purposes, not con-
trol of relays or loop current.
Change Password
Allows for a change of password. Requires the Sup Pswd.
Change Sup Password
Allows for a change of Sup Pswd. Requires the Sup Pswd.
Previous Menu
Returns to the current menu, Calibration.
Press DOWN arrow to proceed to Diagnostics.
22