UNIT CONFIGURATION cont.
SYSTEM CONFIG MENU cont.
Volume and Level Measurement
This menu is used to configure the main control parameters
of the Series 801 for volume and level measurements.
For the purposes of this manual and to become familiar with
the configuration parameters of this unit, all instructions will
be shown. It is important to note that once in the System
Config menu, you may scroll through the selections by using
the UP or DOWN arrow. Once the desired selection is dis-
played, press ENT. The unit is capable of being configured in
three different modes of operation.
• Level Only
• Volume & Level
• Flow & Level
The menu layout for Volume and Level Measurement is
shown below.
Series 801
Measured Values
System Config - Volume and Level
Measurement
Unit Operation
Level Units
Mode Setup
Vessel Type
Volume Units
Level Limit
Probe Lo Point
Probe Hi Point
Previous Menu
Unit Operation
Single Probe
Dual Probe
Difference (1-2)
Summing (1+2)
Please refer to the above menu layout for the configura-
tion instructions below.
From the Default Display, press ENT to display Measured
Values. Press the DOWN arrow to display System Config.
Press ENT once again to enter System Config and to display
Unit Operation. Press ENT to display the present configura-
tion. Use the UP or DOWN arrow to scroll through the
options. When the desired selection is displayed, press ENT
to store the value. If the mode selection has changed, a
warning will appear:
***WARNING*** This mode change WILL erase ALL set-
tings! Confirm change by pressing <9> will be displayed
if the selection has been changed. Press <9> to confirm.
Supr Password? will be displayed and your chosen pass-
word must be entered at this time. The unit will display the
next menu item - Level Units.
14
SYSTEM CONFIG MENU cont.
Level Units
Inches
Feet
Centimeters
Meters
Press ENT once again to enter System Config and to display
Level Units. Press ENT to display the present units of mea-
surement. Use the UP or DOWN arrow to scroll through units
of measurement. When the desired selection is displayed,
press ENT to store the value. Password? will be displayed if
the selection has been changed and your chosen password
must be entered at this time. The unit will display the next
menu item – Mode Setup.
Refer to Page 7 on selection of a General or Supervisory
Password.
Mode Set Up
Level Only
Volume & Level
Flow & Level
With Mode Set Up displayed, press ENT to display the pre-
sent mode. Scroll UP or DOWN until the desired mode is dis-
played. Press ENT. If the mode selection is changed, a warn-
ing will appear:
***WARNING*** This mode change WILL erase ALL set-
tings! Confirm change by pressing <9> will be displayed
if the selection has been changed. Press <9> to confirm.
Supr Password? will be displayed and your chosen pass-
word must be entered at this time. The unit will display the
next menu item - Vessel Type.
Volume and Level
Vessel Type
Horiz/Flat
Horiz/Elipp.
Horiz/Sphere
Verti/Flat
Verti/Conical
Spherical
Custom Table
With Vessel Type displayed, press ENT to display the
present selection. Use the UP or DOWN arrow to scroll
through the Vessel Type selections. When the desired
vessel is displayed, press ENT.
Enter the values needed to define the vessel parameters (ie.
length, height, radius, end radius, cone, etc.). Refer to
detailed vessel drawings on Page 15 for definitions.
NOTE: For Horiz/Elipp tanks, when END is displayed, enter
the value for one end of vessel only.
When the necessary parameters are entered, the unit will dis-
play the next menu item - Volume Units.