English
Language : 

C0402C150J5GACAUTO Datasheet, PDF (135/148 Pages) Cooper Bussmann, Inc. – Make Wire Connections Simple and Fast
Power Distribution Blocks- Series PDBFS
Series PDBFS
Power Distribution Blocks
Feature/Benefits
Electrical
• Enclosed, safer
• 600Vac or dc (UL 1953), 690Vac or dc (IEC)
installation; IP-20
• IP-20 Finger Safe under specific conditions
finger-safe under specific
• Short-Circuit Current Ratings up to 200,000kA, see table
conditions
• Ampacities up to 760 Amps
• High Short-Circuit Current
• CU Wire range 14 AWG to 500 kcmil or 2.5 to 240 mm2
Ratings up to 200,000A:
PDBs do not have to be
the weak link in achieving
high SCCR for an
industrial control panel
• Small footprint saves
panel space
• Listed to UL1953 which has minimum spacing
requirements at 600V of at least 1” through air and 2” over
surface required for feeders in UL UL508A Industrial
Control Panels
• For 2D CAD drawings visit www.cooperbussmann.com
Mechanical
• DIN rail or panel mount; PDBFS330 & PDBFS504 panel
mount only
• Captive termination screws; screws do not get misplaced
• Wire ready: captive termination screws shipped backed out
to save time on conductor installations
• Sliding DIN rail latch for easy mounting
• Single pole, gang mountable for multiple pole applications
with interlocking dovetail accessory (optional)
• Flammability, UL 94V0
• Tin-plated AL connectors suitable for CU conductors
• Elongated hole for panel mounting; easier mounting with
Agency/Standards
• UL Listed 1953, Guide QPQS, File E256146
• CSA Certified, Class 6228-01, File 15364
• CE component IEC 60947-7-1
• IEC 60529, IP-20 (Finger Safe) under specific wiring
greater flexibility in matching up with drilled panel holes
• Part 2A1279: Interlocking dovetail pin accessory
One pin interlocks two units, two pins to interlock three units
• DIN rail end anchors required to prevent damage to block
when torquing
conditions
Series PDBFS
Catalog
Number
(All Single
Pole)
Amps
Terminal Copper Conductor Capability
Line
Load
Configuration
Wire Range
Wire Range
Openings per Pole
Line Load
Short-Circuit Current Rating Data
Conductors
Max Fuse Class & Amp**
Line
AWG or
kcmil
Load J T
AWG or LPJ JJS
kcmil
JJN
RK1
LPS-RK
LPN-RK
RK5
FRS-R
FRN-R
SCCR
PDBFS204 175A
2/0 - 8 AWG
70 - 10 mm2
2/0 - 8 AWG
70 - 10 mm2
2/0 - 8 2/0 - 8 200 200 100
60 200kA
PDBFS220 175A
2/0 - 8 AWG
70 - 10 mm2
4 - 14 AWG
25 - 2.5 mm2
2/0 - 8
4 - 12
4 - 14
200 200
175† 175†
200† 200†
100†
100†
100†
60† 200kA
60† 100kA
60† 50kA
350kcmil - 6 AWG 350kcmil - 6 AWG
PDBFS303 310A 150 - 16 mm2
150 - 16 mm2
350 - 6 350 - 6 400 400 200 100 200kA
PDBFS330 380A 500kcmil - 6 AWG
240 - 16 mm2
2 - 14 AWG
35 - 2.5 mm2
PDBFS377 570A 300kcmil - 4 AWG
150 - 12 mm2
4 - 14 AWG
25 - 2.5 mm2
350kcmil - 4 AWG 350kcmil - 4 AWG
PDBFS500 620A 185 - 12 mm2
185 - 12 mm2
PDBFS504 760A 500kcmil - 6 AWG 500kcmil - 6 AWG
240 - 16 mm2
240 - 16 mm2
500 - 6
300
300 - 4
350
350 - 4
500
500 - 6
2-6
2 - 14
4-8
4
4 - 14
350
400
200†
175†
600
600†
200†
400
200†
175†
600
600†
200†
600 600
350 - 4 600 800
500 600 800*
600 800*
500 - 6 600 600
200†
100†
100†
400†
400†
100†
400
600
600
600
400
100†
30†
30†
200†
200†
30†
200
200kA
50kA
100kA
200kA
50kA
50kA
200kA
200 100kA
400 200kA
600 100kA
200 100kA
Ampacities 75C per NEC® Table 310.16 and UL508A Table 28.1
*Class L 800A (KRP-C 800_SP) or less fuses suitable for this particular SCCR case.
** Class G 60A (SC-60) or less or Class CC 30A (LP-CC-30, FNQ-R-30, KTK-R-30) or less are suitable for all these SCCRs in this table.
† Higher SCCR may be available, check latest datasheet 1149.
For additional product information, visit www.cooperbussmann.com/magnum
131