2.5.9 Advanced Configuration Menu
This menu is used to set the non-control parameters of the Sentinel II.
Follow this step-by-step procedure to use this menu. It is assumed that you are starting from the
RUN mode.
Current Menu Location
Run
Run/Adv Config
Display
Magnetrol Int’l
x.x level units
Adv Config
> to select
Run/Adv Config/
Damping
Damping (1–60)
6
Action
Normal operation
Access the Adv Config menu
Set the output damping
Run/Adv Config/
Damping
Run/Adv Config/
Default Display
Enter password
Accept the data entered
Default Display
Level
Set the display for the
run mode
Run/Adv Config/
Change Password
Change Password
> to select
Change the unit’s password
Run/Adv Config/
Adjust Loop Pts.
Run/Adv Config/
Adjust Loop Pts.
Run/Adv Config/
Adjust Loop Pts.
Run/Adv Config
Run
Adjust loop pts.
Calibrate the 4–20 mA output
3.5 mA Offset
xxx
22 mA Offset
xxx
Previous Menu
> to select
Magnetrol Int’l
x.x level units
Set the 3.5 mA end point
Set the 22 mA end point
Normal operation
Comments
This is the RUN mode.
Use the arrow keys to scroll down until the
display reads Adv Config.
Set a damping factor to the 4–20 mA output
to decrease the effect of turbulence. Enter the
number of seconds.
The Enter password display will not appear if a
password has been entered anywhere else in the
general program menu. Use the numeric keys
to enter your password.
Set the display variable for the RUN mode.
Press ENT only if you want to change the
password; press the down arrow to skip. Enter
the current system password; press ENT. Then
enter the new password; press ENT. Enter the
new password again; press ENT.
Allows matching of the actual 4–20 mA output
with the displayed value from the measuring
circuit. Adjustment is factory set and typically
will not need to be readjusted.
Use a DMM to measure the actual output current,
increase or decrease the xxx value until DMM
reads 3.5 mA. Press ENT.
Use a DMM to measure the actual output current,
increase or decrease the xxx value until DMM
reads 22 mA. Press ENT. Press DOWN arrow.
Press DEL two times to return to the RUN mode.
This is the RUN mode.
50-604 Kotron Model 804 Sentinel II RF Level Transmitter