Quick calibration menu
2.5.4 QuickCal
The Sentinel II Level Transmitter has a special QuickCal
menu for quick and easy calibration. With this menu,
entry of a low calibration point and a high calibration
point, which correspond to the 4–20 mA span, is possible.
The advantage of QuickCal is that it is not necessary to
enter the general programming menu to perform basic
setup of the unit. Following is the QuickCal menu
structure:
Run Mode:
Warning
Password
Set LO Point
Set HI Point
NOTE: If the QuickCal menu is accidentally pressed, depress the ENT
key (no other keys) three times when the “warning” message
appears.
Following is a step-by-step procedure for using the
QuickCal menu. Before beginning, ensure that level in the
tank is at the low level (4 mA). Begin at the RUN mode:
Key
None
ENT
ENT
ENT
Current Menu
Location
Display
Run
Magnetrol Intl
0.0 level units
Comments
This is RUN mode.
QuickCal
WARNING
SETTINGS
WILL BE LOST
QuickCal
Enter Password
Enter the system password
(factory default is 0804)
QuickCal
Set LO Point
–0
Move the level in the vessel
to desired 4 mA output point.
Enter the actual level
(default units are in inches)
QuickCal
Set HI Point
–0
Move the level in the vessel
to desired 20 mA output
point. Enter the actual level.
ENT
Run
Magnetrol Intl
x.x inches
x.x will correspond to level
in vessel.
50-604 Kotron Model 804 Sentinel II RF Level Transmitter
12