804-R010-330 Datasheet, PDF (20/32 Pages) Magnetrol International, Inc. – Kotron® Sentinel II Model 804 RF Level Transmitter
2.5.8 I/O Configuration Menu (cont.)
The I/O Configuration menu is used to configure the discrete relay output, 4–20 mA output, and
communication parameters of the Sentinel II.
The menu is divided into two tables: Discrete output settings; and 4–20 mA/communications settings.
2.5.8.2 Setting 4–20 mA and communications output
Following is a step-by-step procedure for setting the 4–20 mA and communications output. It is
assumed that you are beginning at the RUN mode.
Current Menu Location
Run
Run/I/O CONFIG
Run/I/O Config/
4–20 mA Settings
Run/I/O Config/
4–20 mA Settings
Display
Magnetrol Int’l
x.x level units
I/O Config
> to select
4–20 mA Settings
> to select
Enable/Disable
Disable
Run/I/O Config/
4–20 mA Settings
4 mA Point
x.xx in
Action
Normal operation
Access the I/O Config menu
Access the 4–20 mA Settings
menu
Activate the 4–20 mA Output
menu
Set the 4 mA level
Run/I/O Config/
4–20 mA Settings
20 mA Point
x.xx in
Set the 20 mA level
Run/I/O Config/
4–20 mA Settings
Fault Mode off
Set the output state on fault
Run/I/O Config/
4–20 mA Settings
Run/I/O Config/Comm
Port Setup
Run/I/O Config/
Comm Port Settings
Run/I/O Config/
Comm Port Settings
Run/I/O Config/
Comm Port Settings
Run/I/O Config/
Comm Port Settings
Run
Previous Menu
x.xx in
Comm Port Setup Access the Comm Port
> to select
Setup menu
Address (0–256)
> to select
Baud rate
9600
Parity
Odd
Previous Menu
> to select
Magnetrol Int’l
x.x level units
Set the unit’s communication
0
Set the unit’s communication
speed
Set the condition of the
parity bit
Normal operation
Comments
This is the RUN mode.
Press the down arrow until the display reads
I/O Config.
Select to use (enable) or bypass (disable) the
4–20 mA output.
Enter the level of the desired 4 mA output.
Enter the level of the desired 20 mA output.
Select the state of the 4–20 mA Output in the event
of a unit fault. Use the arrow keys to select the fault
option (3.5 mA, 22 mA, or HOLD).
Press ENT.
Set a specific address for this device when used
with a digital communications protocol.
This is the I.D. byte used to select this particular
unit during polling.
The selection options are 300, 1200, 4800, 9600.
The selection options are Odd, Even, or None.
Press ENT. Press DEL twice to return to the
RUN mode.
The RUN mode.
17
50-604 Kotron Model 804 Sentinel II RF Level Transmitter