2.5.8 I/O Configuration Menu (cont.)
The I/O Configuration menu is used to configure the discrete relay output, 4â20 mA output, and
communication parameters of the Sentinel II.
The menu is divided into two tables: Discrete output settings; and 4â20 mA/communications settings.
2.5.8.2 Setting 4â20 mA and communications output
Following is a step-by-step procedure for setting the 4â20 mA and communications output. It is
assumed that you are beginning at the RUN mode.
Current Menu Location
Run
Run/I/O CONFIG
Run/I/O Config/
4â20 mA Settings
Run/I/O Config/
4â20 mA Settings
Display
Magnetrol Intâl
x.x level units
I/O Config
> to select
4â20 mA Settings
> to select
Enable/Disable
Disable
Run/I/O Config/
4â20 mA Settings
4 mA Point
x.xx in
Action
Normal operation
Access the I/O Config menu
Access the 4â20 mA Settings
menu
Activate the 4â20 mA Output
menu
Set the 4 mA level
Run/I/O Config/
4â20 mA Settings
20 mA Point
x.xx in
Set the 20 mA level
Run/I/O Config/
4â20 mA Settings
Fault Mode off
Set the output state on fault
Run/I/O Config/
4â20 mA Settings
Run/I/O Config/Comm
Port Setup
Run/I/O Config/
Comm Port Settings
Run/I/O Config/
Comm Port Settings
Run/I/O Config/
Comm Port Settings
Run/I/O Config/
Comm Port Settings
Run
Previous Menu
x.xx in
Comm Port Setup Access the Comm Port
> to select
Setup menu
Address (0â256)
> to select
Baud rate
9600
Parity
Odd
Previous Menu
> to select
Magnetrol Intâl
x.x level units
Set the unitâs communication
0
Set the unitâs communication
speed
Set the condition of the
parity bit
Normal operation
Comments
This is the RUN mode.
Press the down arrow until the display reads
I/O Config.
Select to use (enable) or bypass (disable) the
4â20 mA output.
Enter the level of the desired 4 mA output.
Enter the level of the desired 20 mA output.
Select the state of the 4â20 mA Output in the event
of a unit fault. Use the arrow keys to select the fault
option (3.5 mA, 22 mA, or HOLD).
Press ENT.
Set a specific address for this device when used
with a digital communications protocol.
This is the I.D. byte used to select this particular
unit during polling.
The selection options are 300, 1200, 4800, 9600.
The selection options are Odd, Even, or None.
Press ENT. Press DEL twice to return to the
RUN mode.
The RUN mode.
17
50-604 Kotron Model 804 Sentinel II RF Level Transmitter
|
▷ |