2.5.8 I/O Configuration Menu
The I/O Configuration menu is used to configure the discrete relay output, 4–20 mA output, and
communication parameters of the Sentinel II.
The menu is divided into two tables: Discrete output settings; and 4–20 mA/communications settings.
2.5.8.1 Discrete output settings
Follow the step-by-step procedure for setting the discrete output. It is assumed that you are starting
from the RUN mode.
Current Menu Location
Run
Run/I/O CONFIG
Run/I/O Config/
Relay Settings
Display
Magnetrol Int’l
x.x level units
I/O Config
> to select
Relay Settings
> to select
Run/I/O Config/
Relay Settings
Select Relay
> to select
Run/I/O Config/
Relay Settings
Select Relay
Run/I/O Config/
Relay Settings
Select Relay
Run/I/O Config/
Relay Settings
Select Relay
Run/I/O Config/
Relay Settings
Select Relay
Run/I/O Config/
Relay Settings
Select Relay
Run/I/O Config/
Relay Settings
Select Relay
Run/I/O Config/
Relay Settings
Select Relay
Run/I/O Config/
Relay Settings
Select Relay
Run/I/O Config/
Relay Settings
Run/I/O Config/
Relay Settings
Run/I/O Config/
Relay Settings
Lead Lag Mode
Run/I/O Config/
Relay Settings
Run/I/O Config/
Relay Settings
Run
Fault Relay (#1)
Disable
Enable/disable
disable
Relay On point
X.XX in
Relay Off point
X.XX in
Fail-safe
DNRG>Set point
Relay On Delay
1 sec
Relay Off Delay
1 sec
Fault Mode
DNRG on fault
Previous Menu
> to select
Select Relay
> to select
Lead Lag Mode
DNRG>Set point
Previous Menu
> to select
Relay Settings
> to select
Magnetrol Int’l
x.x level units
Action
Comments
Normal operation
This is the RUN mode.
Access the I/O Config menu
Access the Relay Settings
menu
Select the relay to configure
Select relay #1 as the fault relay
Use the arrow keys to scroll down until the
display reads I/O Config.
This menu allows you to set all discrete output
parameters (Relay).
This menu allows you to set specific parameters
concerning individual set points. Enter the
discrete output number (1–4).
NOTE: If you enabled Relay #1 as the fault relay,
control output options are (2–4).
This display will only appear if Relay #1 is selected
in the preceding step. Select Relay #1 as the fault
relay (enable) or as a standard discrete output
(disable)
Activate the relay
Select to use (enable) or bypass (disable) this
output.
Set the relay energize point
Enter the level at which you want the output
to energize.
Set the relay de-energize point
Select the fail-safe condition
Set the relay energize delay
Enter the level at which you want the output
to de-energize.
This step will only appear if the Relay On and
Relay Off points are the same. Select either
DNRG<Set point (low level fail-safe) or
DNRG>Set point (high level fail-safe).
Enter the desired delay period before the relay
energizes.
Set the relay de-energize delay
Enter the desired delay period before the relay
de-energizes.
Select the output state on fault
Select whether the control output will de-energize
on a system fault or hold the latest output.
Set the Lead/Lag relay
combinations
Normal operation
This menu allows you to select various options
concerning multiple pump sequencing. Use the
arrow keys to select the various pump sequencing
options (1-2, 1-2-3, 1-2-3-4, etc.). If relay #1 was
selected as the fault relay, options containing 1 will
not be available.
Press the down arrow to setup the 4–20 mA
output or communications options (the next table)
or press DEL two times to return to the RUN mode.
The RUN mode.
50-604 Kotron Model 804 Sentinel II RF Level Transmitter