How to Recover From a Lost Password
You can use a local computer, a computer that connects to the unit or
other device through the serial port to access the control console.
1. Select a serial port at the local computer, and disable any service
that uses that port.
2. Connect the serial cable (940-0103) to the selected port on the
computer and to the configuration port at the unit:
3. Run a terminal program (such as HyperTerminal®) on your
computer and configure the selected port as follows:
– 9600 bps
– 8 data bits
– no parity
– 1 stop bit
– no flow control.
4. Press ENTER, repeatedly if necessary, to display the User Name
prompt. If you are unable to display the User Name prompt, verify
the following:
– The serial port is not in use by another application.
– The terminal settings are correct as specified in step 3.
– The correct cable is being used as specified in step 2.
5. Press the Reset button. The Status LED will flash alternately
orange and green. Press the Reset button a second time
immediately while the LED is flashing to reset the user name and
password to their defaults temporarily.
6. Press ENTER as many times as necessary to redisplay the User
Name prompt, then use the default, apc, for the user name and
password. (If you take longer than 30 seconds to log on after the
User Name prompt is redisplayed, you must repeat step 5 and log
on again.)
7. From the Control Console menu, select System, then User
Manager.
8. Select Administrator, and change the User Name and Password
settings, both of which are now defined as apc.
9. Press CTRL-C, log off, reconnect any serial cable you disconnected,
and restart any service you disabled.
20
Environmental Monitoring Unit — Installation and Quick Start