AP9319 Datasheet, PDF (12/30 Pages) List of Unclassifed Manufacturers – Environmental Monitoring Unit | |||
|
◁ |
A-Link Connection
Connect to the devices
To connect the Environmental Monitoring Unit to the devices to be
monitored:
1. Set the DIP switch address on each device.
See the manuals included with the individual devices for
configuration information.
See also
2. Connect the first device to either port marked A-Link on the rear
of the unit, using a standard CAT5 (or equivalent) ethernet patch
cable (APC PN 3827BK-10 or equivalent).
3. Cascade additional devices, using CAT5 (or equivalent) cables.
4. Plug an APC terminator (OW 04161) into each of the two
remaining A-Link ports on the rear of the unit and on the last
connected devices.
Maximum combined length of all A-Link cables is 132 ft.
Note
Status RX / TX
Power
Reset
10 = Green
100 = Orange
User Contact Inputs
1 2 34
Temperature/
Humidity
Probe 1 Probe 2
Alarm
Beacon
Output
ï± This port may be used to link to another device or to
plug in an APC terminator (if it is the last device
connected).
ï² Optional device to be monitored by the unit.
ï³ CAT5 (or equivalent) cable connecting to the preceding
optional device in the cascading configuration.
ï´ Optional device to be monitored by the unit.
ïµ CAT5 (or equivalent) cable connecting to the unit.
ï¶ This port may be used to link to another device or to
plug in an APC terminator.
8
Environmental Monitoring Unit â Installation and Quick Start
|
▷ |