AP9319 Datasheet, PDF (20/30 Pages) List of Unclassifed Manufacturers – Environmental Monitoring Unit
Quick Configuration
Control console
2. Use Ping with a size of 113 bytes to assign the IP address defined
by the ARP command. For the IP address defined in step 1, use one
of the following Ping commands:
– Windows command format:
ping 156.205.14.141 -l 113
– LINUX command format:
ping 156.205.14.141 -s 113
3. Use Telnet to access the unit at its newly assigned IP address. For
example:
telnet 156.205.14.141
4. Use apc for both User Name and Password.
5. See “Control console” on page 16 to finish the configuration.
After you log on at the control console, as described in “Local access to
the control console” on page 15 or “Remote access to the control
console” on page 15:
1. Choose Network from the Control Console menu.
2. Choose TCP/IP from the Network menu.
3. If you are not using a BOOTP or DHCP server to configure the
TCP/IP settings, select the Boot Mode menu. Select Manual boot
mode, and then press ESC to return to the TCP/IP menu. (Changes
will take effect when you log out.)
4. Set the System IP, Subnet Mask, and Default Gateway address
values.
5. Press CTRL-C to exit to the Control Console menu.
6. Log out (option 4 in the Control Console menu).
If you disconnected a cable during the procedure
described in “Local access to the control console” on
page 15, reconnect that cable and restart the associated
Note service.
16
Environmental Monitoring Unit — Installation and Quick Start