English
Language : 

QT40.361 Datasheet, PDF (7/27 Pages) PULS GmbH – THREE PHASE INPUT
Q-Series
QT40.361
36V, 26.7A, THREE PHASE INPUT
Fig. 6-1 Output voltage vs. output current in
“single use” mode, typ.
Output Voltage
42V
A
36
30
24
18
A Continuously
available
12
B
Short-term (4s)
BonusPower
6
0
0
10 20
Adjustment Range
B
A
B
30 40 50A
Output Current
Fig. 6-3 Bonus time vs. output power
Bonus Time
5s
4
3
max.
min.
2
1
Output Power
0
100 110 120 130 140 150 160 170%
Fig. 6-5 BonusPower® recovery time
Power
Demand
100%
Limitation by
Power Manager
Output
Voltage
t
Bonus
Time
Recovery Time
Bonus Power disabled
t
Fig. 6-2 Output voltage vs. output current in
“parallel use” mode, typ.
Output Voltage (Parallel Use, typ.)
46V
Adjustment Range
44V
42V
40V
38V
Factory
A
B
setting
36V
A
Continuously
available
34V
32V
B
Short-term (4s)
BonusPower
0
10
20
A
B
30
40A
Output Current
Fig. 6-4 Dynamic overcurrent capability, typ.
Output Voltage (dynamic behavior, < 25ms)
42V
36
Adjustment
Range
30
24
18
12
6
Output Current
0
0 10 20 30 40 50 60 70 80 90A
The BonusPower® is available as soon as power comes on and after the end of an output short circuit or output
overload.
Fig. 6-6 BonusPower® after input turn-on
Fig. 6-7 BonusPower® after output short
Input
Voltage
Output
Voltage
100%
Output
Power
150% Bonus
Power
Output
Voltage
Short of
Output
Output
Power
150%
Bonus
Power
100%
Dec. 2016 / Rev. 1.3 DS-QT40.361-EN
All parameters are specified at 36V, 26.7A, 3x400Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
7/27