QT40.361 Datasheet, PDF (11/27 Pages) PULS GmbH – THREE PHASE INPUT
Q-Series
QT40.361
36V, 26.7A, THREE PHASE INPUT
11. EFFICIENCY AND POWER LOSSES
Efficiencies for 3-Phase operation:
3AC 400V 3AC 480V
Efficiency
typ.
95.3%
95.2%
at 36V, 26.7A
Average efficiency*)
typ.
94.7%
94.6%
25% at 6.7A, 25% at 13.3A, 25% at 20A.
25% at 26.7A
Power losses
typ.
1.5W
1.5W
with activated shut-down
typ.
9.5W
9.8W
at 36V, 0A (no load)
typ.
24.1W
25.0W
at 36V, 13.3A (half load)
typ.
47.3W
48.4W
at 36V, 26.7A (full load)
*) The average efficiency is an assumption for a typical application where the power supply is loaded with 25% of the nominal load for 25%
of the time, 50% of the nominal load for another 25% of the time, 75% of the nominal load for another 25% of the time and with 100%
of the nominal load for the rest of the time.
Efficiencies when using only 2 legs of a 3-phase system:
Efficiency
typ.
Power losses
typ.
**) Curves can be found in chapter 24.4
2AC 400V
94.4%**)
56.9W**)
2AC 480V
94.7%**)
53.7W**)
at 36V, 26.7A
at 36V, 26.7A (full load)
Fig. 11-1 Efficiency vs. output current at 36V,
typ.
Efficiency
96%
3x400Vac
95
3x480Vac
94
93
Output Current
92
3 6 9 12 15 18 21 24 27A
Fig. 11-3 Efficiency vs. input voltage at 36V,
26.7A, typ.
Efficiency
95.5%
95.4
95.3
95.2
95.1
95.0
94.9
350
Input Voltage
400 450 500 3x550Vac
Fig. 11-2 Losses vs. output current at 36V,
typ.
Power Losses
60W
50
3x480Vac
40
3x400Vac
30
20
10
Output Current
0
0 3 6 9 12 15 18 21 24 27A
Fig. 11-4 Losses vs. input voltage at 36V,
26.7A, typ.
Power Losses
50W
49
48
47
46
45
44
350
Input Voltage
400 450 500 3x550Vac
Dec. 2016 / Rev. 1.3 DS-QT40.361-EN
All parameters are specified at 36V, 26.7A, 3x400Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
11/27