English
Language : 

QT40.361 Datasheet, PDF (15/27 Pages) PULS GmbH – THREE PHASE INPUT
Q-Series
QT40.361
36V, 26.7A, THREE PHASE INPUT
16. EMC
The power supply is suitable for applications in industrial environment as well as in residential, commercial and light
industry environment without any restrictions. A detailed EMC report is available on request.
All results assume a three phase operation f the power supply.
EMC Immunity
According generic standards: EN 61000-6-1 and EN 61000-6-2
Electrostatic discharge
EN 61000-4-2
contact discharge
air discharge
8kV
15kV
Criterion A
Criterion A
Electromagnetic RF field
EN 61000-4-3
80MHz-2.7GHz
10V/m
Criterion A
Fast transients (Burst)
Surge voltage on input
EN 61000-4-4
input lines
4kV
output lines
2kV
DC-OK signal (coupling clamp)
2kV
EN 61000-4-5
L1 Æ L2, L2 Æ L3, L1 Æ L3
2kV
L1 / L2 / L3 Æ PE
4kV
Criterion A
Criterion A
Criterion A
Criterion A
Criterion A
Surge voltage on output
EN 61000-4-5
+Æ-
+ / - Æ PE
1kV
Criterion A
1kV
Criterion A
Surge voltage on DC-OK
EN 61000-4-5
DC-OK signal Æ PE
1kV
Criterion A
Conducted disturbance
EN 61000-4-6
0.15-80MHz
10V
Criterion A
Mains voltage dips
(Dips on three phases)
EN 61000-4-11
0% of 380Vac (0Vac)
0% of 480Vac (0Vac)
0Vac, 20ms
0Vac, 20ms
Criterion A,
Criterion A
Mains voltage dips
(Dips on two phases)
EN 61000-4-11
40% of 380Vac (152Vac)
40% of 480Vac (192Vac)
70% of 380Vac (266Vac)
70% of 480Vac (336Vac)
200ms
200ms
500ms
500ms
Criterion A
Criterion A
Criterion A
Criterion A
Voltage interruptions
EN 61000-4-11 0% of 200Vac (=0V)
5000ms
Criterion C
Voltage sags
SEMI F47 0706 dips on two phases according to section 7.2. of the SEMI F47 standard
80% of 380Vac (304Vac)
70% of 380Vac (266Vac)
50% of 380Vac (160Vac)
1000ms
500ms
200ms
Criterion A
Criterion A
Criterion A
Powerful transients
VDE 0160
over entire load range
1550V, 1.3ms
Criterion A
Criterions:
A: Power supply shows normal operation behavior within the defined limits.
C: Temporary loss of function is possible. Power supply may shut-down and restarts by itself. No damage or hazards for the power supply
will occur.
EMC Emission
According generic standards: EN 61000-6-3 and EN 61000-6-4
Conducted emission
input lines
EN 55011, EN 55022, FCC Part 15, CISPR 11, CISPR 22 Class B
Conducted emission
output lines
IEC/CISPR 16-1-2, IEC/CISPR 16-2-1
5dB higher than average limits
for DC power port according EN
61000-6-3**)
Radiated emission
EN 55011, EN 55022
Class B
Harmonic input current
EN 61000-3-2
fulfilled for class A equipment
Voltage fluctuations, flicker EN 61000-3-3
fulfilled*)
This device complies with FCC Part 15 rules.
Operation is subjected to following two conditions: (1) this device may not cause harmful interference, and (2) this
device must accept any interference received, including interference that may cause undesired operation.
*) Tested with constant current loads, non pulsing
**) Restrictions apply for applications in residential, commercial and light-industrial environments, where local DC power networks according
to EN 61000-6-3 are involved. No restrictions for all kinds of industrial applications.
Dec. 2016 / Rev. 1.3 DS-QT40.361-EN
All parameters are specified at 36V, 26.7A, 3x400Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
15/27