QT40.361 Datasheet, PDF (12/27 Pages) PULS GmbH – THREE PHASE INPUT
Q-Series
QT40.361
36V, 26.7A, THREE PHASE INPUT
12. LIFETIME EXPECTANCY AND MTBF
3AC 400V
3AC 480V
Calculated lifetime expectancy*)
363 000h*)
360 000h*)
at 36V, 13.3A and 25°C
128 000h
127 000h
at 36V, 13.3A and 40°C
202 000h*)
203 000h*)
at 36V, 26.7A and 25°C
71 000h
72 000h
at 36V, 26.7A and 40°C
MTBF**) SN 29500, IEC 61709
375 000h
369 000h
at 36V, 26.7A and 40°C
685 000h
678 000h
at 36V, 26.7A and 25°C
MTBF**) MIL HDBK 217F
158 000h
157 000h
at 36V, 26.7A and 40°C; Ground Benign GB40
211 000h
210 000h
at 36V, 26.7A and 25°C; Ground Benign GB25
*) The calculated lifetime expectancy shown in the table indicates the minimum operating hours (service life) and is determined by the
lifetime expectancy of the built-in electrolytic capacitors. Lifetime expectancy is specified in operational hours and is calculated according
to the capacitor’s manufacturer specification. The manufacturer of the electrolytic capacitors only guarantees a maximum life of up to 15
years (131 400h). Any number exceeding this value is a calculated theoretical lifetime which can be used to compare devices.
**) MTBF stands for Mean Time Between Failure, which is calculated according to statistical device failures, and indicates reliability of a
device. It is the statistical representation of the likelihood of a unit to fail and does not necessarily represent the life of a product.
The MTBF figure is a statistical representation of the likelihood of a device to fail. A MTBF figure of e.g. 1 000 000h means that
statistically one unit will fail every 100 hours if 10 000 units are installed in the field. However, it can not be determined if the failed unit
has been running for 50 000h or only for 100h.
13. FUNCTIONAL DIAGRAM
Fig. 13-1 Functional diagram
L1
Input Fuses
L2
L3
Input Filter
Input Rectifier
Inrush Limiter
PFC
Converter
Transient Filter
Output
Voltage
Regulator
Power
Converter
Output
Filter
Temper-
ature
Shut-
down
Output
Power
Manager
Output
Over-
Voltage
Protection
Output
Voltage
Monitor
DC ok
Relay
Shut-
down
Single /
Parallel
VOUT
+
+
-
-
Overload
LED
DC-ok
LED
13
DC-ok
14 Contact
15 Shut-
down
16 Input
Dec. 2016 / Rev. 1.3 DS-QT40.361-EN
All parameters are specified at 36V, 26.7A, 3x400Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany