QT40.361 Datasheet, PDF (27/27 Pages) PULS GmbH – THREE PHASE INPUT
Q-Series
QT40.361
36V, 26.7A, THREE PHASE INPUT
24.13.MOUNTING ORIENTATIONS
Mounting orientations other than all terminals on the bottom require a reduction in continuous output power or a
limitation in the maximum allowed ambient temperature. The amount of reduction influences the lifetime expectancy
of the power supply. Therefore, two different derating curves for continuous operation can be found below:
Curve A1
Curve A2
Recommended output current.
Max allowed output current (results in approximately half the lifetime expectancy of A1).
Fig. 24-10
Mounting
Orientation A
(Standard
orientation)
Power
Supply
INPUT OUTPUT
Output Current
28A
A1
21
14
7
0
Ambient Temperature
10 20 30 40 50
60°C
Fig. 24-11
Mounting
Orientation B
(Upside down)
Output Current
28A
21
A2
14
A1
7
0
Ambient Temperature
10 20 30 40 50
60°C
Fig. 24-12
Mounting
Orientation C
(Table-top
mounting)
Output Current
28A
21
A2
14
A1
7
0
Ambient Temperature
10 20 30 40 50
60°C
Fig. 24-13
Mounting
Orientation D
(Horizontal cw)
Output Current
28A
21
14
7
0
10
A2
A1
Ambient Temperature
20 30 40 50
60°C
Fig. 24-14
Mounting
Orientation E
(Horizontal ccw)
Output Current
28A
21
14
7
0
10
A2
A1
Ambient Temperature
20 30 40 50
60°C
Dec. 2016 / Rev. 1.3 DS-QT40.361-EN
All parameters are specified at 36V, 26.7A, 3x400Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
27/27