QT40.361 Datasheet, PDF (17/27 Pages) PULS GmbH – THREE PHASE INPUT
Q-Series
QT40.361
36V, 26.7A, THREE PHASE INPUT
18. PROTECTION FEATURES
Output protection
Electronically protected against overload, no-load and short-circuits*)
Output over-voltage protection typ. 45.5Vdc
max. 48Vdc
In case of an internal power supply defect, a redundant
circuit limits the maximum output voltage. The output
shuts down and automatically attempts to restart.
Degree of protection
IP 20
EN/IEC 60529
Caution: For use in a controlled environment according
to CSA 22.2 No 107.1-01.
Penetration protection
> 5mm
e.g. screws, small parts
Over-temperature protection
yes
Output shut-down with automatic restart
Input transient protection
MOV (Metal Oxide Varistor)
Internal input fuse
included
not user replaceable
*) In case of a protection event, audible noise may occur.
19. SAFETY FEATURES
Input / output separation*)
Class of protection
Isolation resistance
PE resistance
Touch current (leakage current)
*) double or reinforced insulation
SELV
IEC/EN 60950-1
PELV
IEC/EN 60204-1, EN 50178, IEC 62103, IEC 60364-4-41
double or reinforced insulation
I
PE (Protective Earth) connection required
> 5MOhm
input to output, 500Vdc
< 0.1Ohm
typ. 0.35mA / 0.64mA
3x400Vac, 50Hz, TN-,TT-mains / IT-mains
typ. 0.45mA / 0.91mA
3x480Vac, 60Hz, TN-,TT-mains / IT-mains
max. 0.45mA / 0.78mA
3x440Vac, 50Hz, TN-,TT-mains / IT-mains
max. 0.60mA / 1.20mA
3x528Vac, 60Hz, TN-,TT-mains / IT-mains
Dec. 2016 / Rev. 1.3 DS-QT40.361-EN
All parameters are specified at 36V, 26.7A, 3x400Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
17/27