5.0 E3 Modulevel Menu: Step by Step Procedures
The following table describes the software menu displayed
by the E3 Modulevel FOUNDATION fieldbus™ transmitter for
“Level Only” measurement. Use this table as a step by step
guide to configure the transmitter.
The second column presents the menus shown on the trans-
mitter display. The displays are in the order they would
appear if the arrow keys were used to scroll through the
menu. The numbers on the first column are not shown in
the display. They are only provided as reference. The third
column indicates the password level required to access and
change the parameter.
The fourth column provides the actions to take when
configuring the transmitter. Additional information or an
explanation of an action is given in the fifth column.
5.1 Measurement Type: Level Only
Display
*Status*
1
*PV-Lvl*
*AI Out*
Password
None
Action
Transmitter Display
Comment
MeasType = Level
2
PV-Lvl
xx.xx lu
3
AI Out
None
None
Transmitter Display
Transmitter Display
(Alternate Home Menu)
(Alternate Home Menu)
4
Proc SG
x.xxx sg
5
ProcTemp
xxx F
6
LvlUnits
User
User
User
Enter the specific gravity of the Adjusts factory calibration for actual specific gravity
process liquid at operating temp.
Enter the Process Operating Adjusts factory calibration for actual temperature
Temperature
Select the Level Units
Select from cm, inches, feet, meters.
7
Lvl Ofst
xx.xx lu
User
Enter desired level reading Minimum offset = -(displacer length)
when level is at the calibrated Maximum = 960 inches (2438.4 cm)
zero reference
8
LVDT Damp
xx s
9
Trim Lvl
xx.xx lu
10
New Pass
xxx
11
Language
(select)
12
E3 ModFF
Ver 1.0
13
DispFact
(select)
14
History
Status
User
User
User
User
None
None
None
Select time constant of
desired damping
0 to 45 sec
Enter value to adjust Level
reading
Fine tune level reading
-10.00 inch to +10.00 inch
Enter new password (0 – 255) Displays encrypted value of present password
Default value = 0
Select from English, Spanish, Language choice for LCD display
French, German
Transmitter Display
Product identification
Firmware version
Select “Yes” to display factory
parameter menu as below
Diagnostic Display to view
present status and recent
exceptions
48-640 E3 Modulevel Displacer Level Transmitter - FOUNDATION fieldbus™
31