XD_SCALE: The high and low scale values, engineering
units code, and number of digits to the right of the decimal
point used with the value obtained from the transducer for
a specified channel.
OUT_SCALE: The high and low scale values, engineering
units code, and number of digits to the right of the decimal
point to be used in displaying the OUT parameter.
GRANT_DENY: Options for controlling access of host
computers and local control panels to operating, tuning,
and alarm parameters of the block.
IO_OPTS: Option which the user may select to alter input
and output block processing.
STATUS_OPTS: Options which the user may select in the
block processing of status.
CHANNEL: The number of the logical hardware channel
that is connected to this I/O block. This information
defines the transducer to be used going to or from the
physical world.
L_TYPE: Determines if the values passed by the transducer
block to the AI block may be used directly (Direct) or if the
value is in different units and must be converted linearly
(Indirect), or with square root (Ind Sqr Root), using the
input range defined for the transducer and the associated
output range.
LOW_CUT: Limit used in square root processing.
PV_FTIME: Time constant of a single exponential filter for
the PV, in seconds.
FIELD_VAL: Raw value of the field device in % of PV
range, with a status reflecting the Transducer condition,
before signal characterization (L_TYPE) or filtering
(PV_FTIME).
UPDATE_EVT: This alert is generated by any change to
the static data.
BLOCK_ALM: The block alarm is used for all configuration,
hardware, connection failure or system problems in the block.
ALARM_SUM: The current alert status, unacknowledged
states, unreported states, and disabled states of the alarms
associated with the function block.
ACK_OPTION: Selection of whether alarms associated
with the function block will be automatically acknowledged.
ALARM_HYS: Amount the PV must return within the
alarm limits before the alarm condition clears. Alarm hys-
teresis expressed as a percent of the span of the PV.