LTC4015
DETAILED Register Descriptions
(ARA). See the section Programmable Alerts and Interrupt Controller for more information regarding the SMBALERT
and ARA functions.
meas_sys_valid_alert (Sub-Address 0x36, Bit 15, R/Clear)
To achieve high measurement accuracy, the measurement system in the LTC4015 has a typical warm up time of
approximately 12ms. If en_meas_sys_valid_alert=1, the meas_sys_valid_alert bit indicates that an SMBALERT has
occurred because the warm-up period has passed and the A/D measurement system results are valid. This can be
particularly useful in battery only mode for periodic sampling of the measurement system; see force_meas_sys_on
for more information.
qcount_lo_alert (Sub-Address 0x36, Bit 13, R/Clear)
If en_qcount_lo_alert=1, this bit indicates that an SMBALERT has occurred because QCOUNT has fallen below
QCOUNT_LO_ALERT_LIMIT.
qcount_hi_alert (Sub-Address 0x36, Bit 12, R/Clear)
If en_qcount_hi_alert=1, this bit indicates that an SMBALERT has occurred because QCOUNT has exceeded
QCOUNT_HI_ALERT_LIMIT.
vbat_lo_alert (Sub-Address 0x36, Bit 11, R/Clear)
If en_vbat_lo_alert =1, this bit indicates that an SMBALERT has occurred because VBAT has fallen below VBAT_
LO_ALERT_LIMIT.
vbat_hi_alert (Sub-Address 0x36, Bit 10, R/Clear)
If en_vbat_hi_alert =1, this bit indicates that an SMBALERT has occurred because VBAT has exceeded VBAT_HI_
ALERT_LIMIT.
vin_lo_alert (Sub-Address 0x36, Bit 9, R/Clear)
If en_vin_lo_alert =1, this bit indicates that an SMBALERT has occurred because VIN has fallen below VIN_LO_
ALERT_LIMIT.
vin_hi_alert (Sub-Address 0x36, Bit 8, R/Clear)
If en_vin_hi_alert =1, this bit indicates that an SMBALERT has occurred because VIN has exceeded VIN_HI_ALERT_
LIMIT.
vsys_lo_alert (Sub-Address 0x36, Bit 7, R/Clear)
If en_vsys_lo_alert =1, this bit indicates that an SMBALERT has occurred because VSYS has fallen below VSYS_
LO_ALERT_LIMIT.
vsys_hi_alert (Sub-Address 0x36, Bit 6, R/Clear)
If en_vsys_hi_alert =1, this bit indicates that an SMBALERT has occurred because VSYS has exceeded VSYS_HI_
ALERT_LIMIT.
iin_hi_alert (Sub-Address 0x36, Bit 5, R/Clear)
If en_iin_hi_alert =1, this bit indicates that an SMBALERT has occurred because IIN has exceeded IIN_HI_ALERT_LIMIT.
ibat_lo_alert (Sub-Address 0x36, Bit 4, R/Clear)
If en_ibat_lo_alert =1, this bit indicates that an SMBALERT has occurred because IBAT has fallen below IBAT_LO_
ALERT_LIMIT.
4015f
68