US10D10A00 Datasheet, PDF (3/94 Pages) Honeywell Solid State Electronics Center – Basic Switches | |||
|
◁ |
Basic Switches
Standard
ELECTRICAL DATA AND UL CODES STANDARD BASIC
SWITCHES
Most of the switches in this section are UL recognized and CSA
certified. The current and voltage values shown are based on
test conditions specified by these agencies. Electrical life of the
switch is influenced by each application condition as well as by
voltage and current. For application assistance contact the 800
number.
Circuitry
Single-pole
double-throw
unless
otherwise noted
in order guide
Single-pole
double-throw
unless
otherwise noted
in order guide
Single-pole
double-throw
unless
otherwise noted
in order guide
Single-pole
double-throw
unless
otherwise noted
in order guide
Single-pole
double-throw
unless
otherwise noted
in order guide
Single-pole
double-throw
unless
otherwise noted
in order guide
Single-pole
double-throw
unless
otherwise noted
in order guide
Single-pole
double-throw
unless
otherwise noted
in order guide
Single-pole
double-throw
unless
otherwise noted
in order guide
Electrical Data and
UL Codes
A 15 amps, 125, 250 or 480 vac;
1â8 hp, 125 vac; 1â4 hp, 250 vac;
1â2 amp, 125 vdc; 1â4 amp,
250 vdc.
UL Code L96
B 5 amps, 125, 250 or 480 vac;
1â2 amp, 125 vdc; 1â4 amp, 250 vdc.
UL Code L35
C 10 amps, 125, 250 or 480 vac;
UL Code L8
D 15 amps, 125, 250 or 480 vac;
1â8 hp, 125 vac; 1â4 hp, 250 vac.
UL Code L103
E 15 amps, 125, 250 or 480 vac;
1â4 hp, 125 vac, 1â2 hp, 250 vac;
1â2 amp, 125 vdc; 1â4 amp, 250 vdc.
UL Code L67
F 22 amps, 125, 250 or 480 vac;
1â2 hp, 125 vac, 1 hp, 250 vac.
UL Code L161
G 20 amps, 125, 250 or 480 vac;
10 amps, 125 vac ââLââ (tungsten
lamp load);
1 hp, 125 vac; 2 hp, 250 vac;
1â2 amp, 125 vdc; 1â4 amp,
250 vdc.
UL Code L23
H Motor Control
25 amps, 125, 250 or 480 vac;
1 hp, 125 vac; 2 hp, 250 vac;
Pilot Dutyâ750 VA, 125, 250,
or 277 vac.
I 10 amps, 125, 250 or 480 vac;
1â8 hp, 125 vac; 1â4 hp, 250 vac;
UL Code L95
Circuitry
Double-pole
double-throw
Electrical Data and
UL Codes
J 10 amps, 125 or 250 vac;
0.3 amp, 125 vdc; 0.15 amp,
250 vdc.
UL Code L59
Single-pole
double-throw
unless
otherwise noted
in order guide
K Rating established with
switch non-polarized
10 amps, 125 vac or vdc;
1â4 hp, 125 vac or vdc.
UL Code L 168
Non-polarized:
10 amps res. or 1â4 hp, 125 vdc;
3 amps max. res. 250 vdc.
Polarized*:
10 amps res. or 1â2 hp, 125 vdc;
3 amps max. res., 250 vdc.
*To polarize, connect negative side of line to common terminal. To
achieve the same effect, mount switch with brass screws, using a
non-magnetic barrier (at least 1â4 ⯠thick) between the switch and
mounting surface.
Two-circuit
double-break
M 25 amps, 125, 250 or 480 vac;
3â4 hp, 125 vac; 11â4 amp, 250 vac.
1 amp, 125 vdc; 1â2 amp, 250 vdc.
UL Code L58
Single-pole
double-throw
P 1 amp, 125 VAC
UL Code L22
Single-pole
double-throw
R 10 amps, 125 or 250 vac;
1â3 hp, 125 vac; 3â4 hp, 250 vac;
1â2 amp, 125 vdc; 1â4 amp,
250 vdc.
UL Code L115
Single-pole
double-throw
S 10 amps, 125 or 250 vac;
1â3 hp, 125 or 250 vac.
UL Code L93
Two-circuit
double-break
Single-pole
double-throw
T 15 amps, 125, 250 or 480 vac;
1 amp, 125 vdc; 1â2 amp, 250 vdc;
1â4 hp, 125 vac; 1â2 hp, 250 vac
UL Code L73
U 5 amps, 250 vac.
UL Code L4
Two-circuit
double-break
V Motor Control
15 amps, 120, 240, 480 or 600
vac;
1â2 hp, 120 vac; 1 hp, 240 vac;
0.8 amp, 115 vdc; 0.4 amp,
230 vdc.
Single-pole
single-throw
(N.C.)
Single-pole
double-throw
W 20 amps, 125, 250 or 277 vac;
3â4 hp, 125 vac; 1â2 hp, 250 vac
UL Code L178B
X 15 amps, 125, 250 or 480 vac;
2 amps, 600 vac;
1â8 hp, 125 vac; 1â4 hp, 250 vac;
1â2 amp, 125 vdc; 1â4 amp,
250 vdc.
UL Code L74
Single-pole
double-throw
Y 20 amps, 125, 250 or 480 vac;
3â4 hp, 125 vac; 11â2 hp, 250 vac; UL
Code L17
46 Honeywell Sensing and Control
For application help: call 1-800-537-6945.
|
▷ |