CT5.241 Datasheet, PDF (6/21 Pages) PULS GmbH – 24V, 5A, TWO-PHASE INPUT
C-Series
CT5.241
24V, 5A, TWO-PHASE INPUT
6. OUTPUT
Output voltage
Adjustment range
Factory setting
Line regulation
Load regulation
Ripple and noise voltage
Output capacitance
Output current
Output power
Short-circuit current
nom.
min.
max.
max.
max.
max.
typ.
nom.
nom.
nom.
nom.
nom.
nom.
min.
max.
24V
24-28V
30V
24.1V
10mV
100mV
50mVpp
3 800μF
6A
5A
5.2A
4.3A
144W
120W
10A
13A
Fig. 6-1 Output voltage vs. output current,
typ.
Output Voltage
28V
24
20
16
12
8
4
0
02
Adjustment
Range
Output Current
4 6 8 10 12A
guaranteed
at clockwise end position of potentiometer
±0.2%, at full load, cold unit
323-576Vac
static value, 0A Æ 5A
20Hz to 20MHz, 50Ohm
at 24V, ambient < 45°C, see Fig. 6-1
at 24V, ambient < 60°C, see Fig. 6-1
at 28V, ambient < 45°C, see Fig. 6-1
at 28V, ambient < 60°C, see Fig. 6-1
for ambient temperatures < 45°C
for ambient temperatures < 60°C
continuous current, short circuit impedance 200mOhm
continuous current, short circuit impedance 200mOhm
Peak current capability (up to several milliseconds)
The power supply can deliver a peak current which is higher than the specified short term current. This helps to start
current demanding loads or to safely operate subsequent circuit breakers.
The extra current is supplied by the output capacitors inside the power supply. During this event, the capacitors will be
discharged and causes a voltage dip on the output. Detailed curves can be found in chapter 23.1.
Peak current voltage dips
typ. from 24V to 18.5V at 10A for 50ms, resistive load
typ. from 24V to 13V at 25A for 2ms, resistive load
typ. from 24V to 7V
at 25A for 5ms, resistive load
Jan. 2010 / Rev. 1.1 DS-CT5.241-EN
All parameters are specified at 24V, 5A, 400Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
6/21