English
Language : 

CT5.241 Datasheet, PDF (18/21 Pages) PULS GmbH – 24V, 5A, TWO-PHASE INPUT
C-Series
CT5.241
24V, 5A, TWO-PHASE INPUT
23.3. CHARGING OF BATTERIES
The power supply can be used to charge lead-acid or maintenance free batteries. (Two 12V batteries in series)
Instructions for charging batteries:
a) Ensure that the ambient temperature of the power supply is below 45°C
b) Set output voltage (measured at no load and at the battery end of the cable) very precisely to the end-of-charge
voltage.
End-of-charge voltage
27.8V
27.5V
27.15V
26.8V
Battery temperature
10°C
20°C
30°C
40°C
c) Use a 10A circuit breaker (or blocking diode) between the power supply and the battery.
d) Ensure that the output current of the power supply is below the allowed charging current of the battery.
e) Use only matched batteries when putting 12V types in series.
f) The return current to the power supply (battery discharge current) is typ. 5.5mA when the power supply is
switched off (except in case a blocking diode is utilized).
23.4. OUTPUT CIRCUIT BREAKERS
Standard miniature circuit breakers (MCB’s or UL1077 circuit breakers) are without doubt, one of the most efficient
and economical ways to open circuits on faulty branches. Most of these breakers may also be used on 24V branches.
MCB’s are designed to protect wires and circuits. If the ampere value and the characteristics of the MCB are adapted to
the wire size that is used, the wiring is considered as thermally safe regardless of whether the MCB opens or not.
To avoid voltage dips and under-voltage situations in adjacent 24V branches which are supplied by the same source, a
fast (magnetic) tripping of the MCB is desired. A quick shutdown within 10ms is necessary corresponding roughly to
the ride-through time of PLC's. This requires power supplies with high current reserves and large output capacitors.
Furthermore, the impedance of the faulty branch must be sufficiently small in order for the current to actually flow.
The best current reserve in the power supply does not help if Ohm’s law does not permit current flow. The following
table has typical test results showing which B- and C-Characteristic MCBs magnetically trip depending on the wire cross
section and wire length.
Fig. 23-3 Test circuit
Maximal wire length for a magnetic (fast) tripping *):
0.75mm² 1.0mm² 1.5mm² 2.5mm²
Power Supply MCB
Load
C-2A
17m
19m
29m
39m
AC
+
+
C-3A
11m
14m
22m
33m
DC -
Wire length
S1
-
C-4A
3m
4m
6m
14m
C-6A
1m
1m
2m
3m
C-8A
-
-
-
-
S1... Fault simulation switch
B-6A
6m
9m
13m
17m
B-10A
-
-
-
1m
*) Don’t forget to consider two times the distance to the load (or cable length) when calculating the total wire length (+ and – wire).
23.5. INDUCTIVE AND CAPACITIVE LOADS
The unit is designed to supply any kind of loads, including unlimited capacitive and inductive loads.
Jan. 2010 / Rev. 1.1 DS-CT5.241-EN
All parameters are specified at 24V, 5A, 400Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
18/21