CT5.241 Datasheet, PDF (5/21 Pages) PULS GmbH – 24V, 5A, TWO-PHASE INPUT
C-Series
CT5.241
24V, 5A, TWO-PHASE INPUT
4. DC-INPUT
DC input
DC input range
Allowed Voltage Line to Earth
DC input current
Turn-on voltage
Shut-down voltage
nom.
max.
typ.
typ.
typ.
DC 600V
450-780Vdc
820Vdc
0.3A / 0.17A
370Vdc
260Vdc
continuous operation
IEC 62103
450Vdc / 780Vdc, 24V, 5A
steady state value
steady state value
Fig. 4-1 Wiring for DC Input
Battery
Power Supply
+
AC
FUSE
L1
FUSE
L2
+
-
PE
-
DC
Load
Instructions for DC use:
a) Use a battery or similar DC source.
For other sources contact PULS
b) Connect +pole to L1 and –pole to L2.
c) Use appropriate external fuses in the + and – lines which
are suitable for the DC-voltage.
d) Connect the PE terminal to a earth wire or to the machine
ground.
e) DC-operation is not included in the UL approval.
Additional testing might be necessary.
5. INPUT INRUSH CURRENT
An active inrush limitation circuit limits the input inrush current after turn-on of the input voltage and after short
input voltage interruptions.
The charging current into EMI suppression capacitors is disregarded in the first microseconds after switch-on.
Inrush current
Inrush energy
max.
typ.
max.
AC 400V
10Apeak
4Apeak
0.5A2s
AC 480V
10Apeak
4Apeak
0.5A2s
-25°C to +70°C
-25°C to +70°C
-25°C to +70°C
Fig. 5-1 Input inrush current, typical behavior
Input Current
1>
Input Voltage
3>
Output Voltage
2 >2
20ms / DIV
Input:
Output:
Ambient:
400Vac
24V, 5A
25°C
Upper curve:
Middle curve:
Lower curve:
Time basis:
Input current 2A / DIV
Input voltage 500V / DIV
Output voltage 10V / DIV
20ms / DIV
Jan. 2010 / Rev. 1.1 DS-CT5.241-EN
All parameters are specified at 24V, 5A, 400Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.