CT5.241 Datasheet, PDF (10/21 Pages) PULS GmbH – 24V, 5A, TWO-PHASE INPUT
C-Series
CT5.241
24V, 5A, TWO-PHASE INPUT
11. TERMINALS AND WIRING
Type
Solid wire
Stranded wire
American Wire Gauge
Wire stripping length
Screwdriver
Recommended tightening torque
Input
screw terminals
0.5-6mm2
0.5-4mm2
20-10 AWG
7mm / 0.275inch
3.5mm slotted or
Pozidrive No 2
0.8Nm, 7lb.in
Output
screw terminals
0.5-6mm2
0.5-4mm2
20-10 AWG
7mm / 0.275inch
3.5mm slotted or
Pozidrive No 2
0.8Nm, 7lb.in
Instructions:
a) Use appropriate copper cables that are designed for an operating temperature of:
60°C for ambient up to 45°C and 75°C for ambient up to 60°C minimum.
b) Follow national installation codes and installation regulations!
c) Ensure that all strands of a stranded wire enter the terminal connection!
d) Up to two stranded wires with the same cross section are permitted in one connection point (except PE wire).
e) Do not use the unit without PE connection.
f) Screws of unused terminal compartments should be securely tightened.
g) Ferrules are allowed, but not required
12. RELIABILITY
AC 400V
AC 480V
Lifetime expectancy *)
92 000h
92 000h
at 24V, 5A and 40°C
186 000h
175 000h
at 24V, 2.5A and 40°C
260 000h
260 000h
at 24V, 5A and 25°C
MTBF **) SN 29500, IEC 61709
1 173 000h
1 155 000h at 24V, 5A and 40°C
2 105 000h
2 075 000h at 24V, 5A and 25°C
MTBF **) MIL HDBK 217F
454 000h
446 000h
at 24V, 5A and 40°C; Ground Benign GB40
607 000h
593 000h
at 24V, 5A and 25°C; Ground Benign GB25
*) The Lifetime expectancy shown in the table indicates the minimum operating hours (service life) and is determined by the lifetime
expectancy of the built-in electrolytic capacitors. Lifetime expectancy is specified in operational hours and is calculated according to the
capacitor’s manufacturer specification. The prediction model allows only a calculation of up to 15 years from date of shipment.
**) MTBF stands for Mean Time Between Failure, which is calculated according to statistical device failures, and indicates reliability of a
device. It is the statistical representation of the likelihood of a unit to fail and does not necessarily represent the life of a product.
Jan. 2010 / Rev. 1.1 DS-CT5.241-EN
All parameters are specified at 24V, 5A, 400Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
10/21