CT5.241 Datasheet, PDF (4/21 Pages) PULS GmbH – 24V, 5A, TWO-PHASE INPUT
C-Series
CT5.241
24V, 5A, TWO-PHASE INPUT
3. AC-INPUT
AC input
nom. AC 380-480V
AC input range
323-576Vac
Allowed Voltage Phase to Earth
Input frequency
Turn-on voltage
Shut-down voltage
nom.
typ.
typ.
typ.
typ.
576-700Vac
500Vac
50–60Hz
270Vac
185Vac
220Vac
230Vac
TN, TT, IT-mains networks,
grounding of one phase is allowed except for UL508
applications
continuous operation,
no damage between 0 and 323Vac
for max. 1 second, occasional (not periodical)
IEC 62103
±6%
load independent, see Fig. 3-1
at 24V, 0A, see Fig. 3-1
at 24V, 2.5A
at 24V, 5A
AC 400V
AC 480V
Input current
typ.
0.75A
0.68A
at 24V, 5A, see Fig. 3-3
Power factor *)
typ.
0.45
0.43
at 24V, 5A, see Fig. 3-1
Start-up delay
typ.
75ms
75ms
see Fig. 3-2
Rise time
typ.
35ms
36ms
0mF, 24V, 5A, see Fig. 3-2
typ.
64ms
68ms
5mF, 24V, 5A, see Fig. 3-2
Turn-on overshoot
max.
200mV
200mV see Fig. 3-2
*) The power factor is the ratio of the true (or real) power to the apparent power in an AC circuit.
POUT
Fig. 3-1 Input voltage range
Rated input
range
< 1s
Fig. 3-2 Turn-on behavior, definitions
Input
Voltage
185V 260V 323V
VIN
576V 700Vac
Output
Voltage
- 5%
Start-up Rise
delay Time
Fig. 3-3 Input current vs. output load at 24V
Input Current, typ.
0.8A
0.7
0.6
0.5
4004V8a0cVac
0.4
0.3
0.2
0.1
0
Output Current
0 1 2 3 4 5 6A
Fig. 3-4 Power factor vs. output load
Power Factor, typ.
0.50
0.45
400Vac
480Vac
0.40
0.35
0.30
0
Output Current
1 2 3 4 5 6A
Jan. 2010 / Rev. 1.1 DS-CT5.241-EN
All parameters are specified at 24V, 5A, 400Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany