CT5.241 Datasheet, PDF (13/21 Pages) PULS GmbH – 24V, 5A, TWO-PHASE INPUT
C-Series
CT5.241
24V, 5A, TWO-PHASE INPUT
15. PROTECTION FEATURES
Output protection
Electronically protected against overload, no-load and short-circuits *)
Output over-voltage protection typ. 30.5Vdc
max. 32Vdc
In case of an internal power supply defect, a redundant
circuit limits the maximum output voltage. The output
shuts down and automatically attempts to restart.
Degree of protection
IP 20
EN/IEC 60529
Penetration protection
> 3.5mm
e.g. screws, small parts
Over-temperature protection
yes
output shut-down with automatic restart
Input transient protection
MOV (Metal Oxide Varistor) and active transient filter
Internal input fuse
2x T3.15A H.B.C.
not user replaceable
*) In case of a protection event, audible noise may occur.
16. SAFETY FEATURES
Input / output separation *)
Class of protection
Isolation resistance
PE resistance
Touch current (leakage current)
*) Double or reinforced insulation
SELV
PELV
I
> 5MOhm
< 0.1Ohm
typ. 0.14mA
typ. 0.19mA
< 0.18mA
< 0.25mA
IEC/EN 60950-1
IEC/EN 60204-1, EN 50178, IEC 62103, IEC 60364-4-41
PE (Protective Earth) connection required
input to output, 500Vdc
400Vac, 50Hz, TN mains
480Vac, 60Hz, TN mains
440Vac, 50Hz, TN mains
528Vac, 60Hz, TN mains
17. DIELECTRIC STRENGTH
The output voltage is floating and has no ohmic connection to the ground. Type and factory tests are conducted by
the manufacturer. Field tests may be conducted in the field using the appropriate test equipment which applies the
voltage with a slow ramp (2s up and 2s down). Connect all phase-terminals together as well as all output poles before
conducting the test. When testing, set the cut-off current settings to the value in the table below.
Fig. 17-1 Dielectric strength
Type test
A
60s
2500Vac
B
3000Vac
C
500Vac
Input
L1
L2
B
Output
Factory test
5s
Field test
5s
Cut-off current setting
2500Vac
2000Vac
> 5mA
2500Vac
2000Vac
> 5mA
500Vac
500Vac
> 15mA
A
C
Earth
+
To fulfill the PELV requirements according to EN60204-1 § 6.4.1, we
-
recommend that either the + pole, the – pole or any other part of
the output circuit shall be connected to the protective earth
system. This helps to avoid situations in which a load starts
unexpectedly or can not be switched off when unnoticed earth
faults occur.
Jan. 2010 / Rev. 1.1 DS-CT5.241-EN
All parameters are specified at 24V, 5A, 400Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
13/21