DRQ-12-50-L48 Datasheet, PDF (19/26 Pages) Murata Power Solutions Inc. – 600W Digital Fully Regulated Intermediate DC-DC Bus Converter
DRQ-12/50-L48 Series
OVERALL (CONT.)
Notes:
* Only available in supervisor mode (default state is user mode, send password to comand 0xFC to
change to supervisor mode)
1. a) Unit restores the entire contents of the non-volatile User Store memory when power up
b) PEC is supported
c) Max bus speed: 400kHZ
d) SMBALERT# is supported
e) Linear data format used
f) addressing: If the calculated PMBus address is 0d, 11d or 12d, SA0 or SA1 lefts open, default
PMBus address 120d is assigned instead.
2. Not supported items:
100101XXb Margin Low(Ignore Fault),
101001XXb On Margin High(Ignore Fault)
3. Restart delay of turned off by OPEATION or CONTROL or primary on/off is 200ms
4. Unit will shutdown 1 second for protection , then recover automaticly
5. Restart delay unit: 500ms, lower limit: 500ms.
Turn off delay unit: 0ms, lower limit: 0ms
if bits 7:6=11b, restart delay is 500ms
6. Restart delay unit and Turn off delay unit are same as note 5
Bits 7:6: 00b,01b,10b are not supported
MURATA-PS defined commands (01-CFh Refer to PMBus 1.2 SPEC)
600W Digital Fully Regulated
Intermediate DC-DC Bus Converter
7. Restart delay unit: 100ms, lower limit: 100ms.
Turn off delay unit:0ms, lower limit: 0ms if bits 7:6=11b, restart delay is 100ms
8. Temperature of baseplate side
9. Temperature of pin side
10. Unit’s actual inforamtion
11. Default value of DROOP CURRENT SHARE mode: 0x01
Default value of CURRENT SHARE DISABLED mode: 0x00
12. Not available in Droop current share mode
13.Locked to 12mΩ in DROOP CURRENT SHARE mode; configurable and default value is 0mΩ in CUR-
RENT SHARE DISABLED mode
14. Default value of negative logic: 0x04
Default value of positive logic: 0x06
15. Unit can receive any value for VOUT_TRIM command, but Vout is limited to 8.1~13.2V, if calculated
Vout exceeds limit, then equal to limit.
16. Value of 0 is acceptable, which is the same as lower limit to unit.
D0h: MFR_VARIABLE_FREQUENCY_DISABLE
Bits
Purpose
Value
Meaning
7:1
0000000 Reserved
0
Variable frequency
control
0
1
Turn on variable frequency control
Turn off variable frequency control
DBh: MFR_CURRENT_SHARE_CONFIG
Bits
Purpose Value
Meaning
7:1
0000000 Reserved
0
Droop Current
Share Control
0 Current share disabled
1 Droop current share mode enabled
DDh: MFR_PRIMARY_ON_OFF_CONFIG
Bits
Purpose Value
Meaning
7:3
00000 Reserved
Controls how the 0 Unit ignores the primary ON/OFF pin
2 unit responds to
the CONTROL pin
1
Unit requires the primary ON/OFF pin to
be asserted to start the unit.
1
Polarity of primary
ON/OFF logic
0
1
Active low (Pull pin low to start the unit)
Active high (Pull high or open to start
the unit)
0
0 Reserved
DEh: MFR_ PGOOD_POLARITY
Bits
Purpose Value
Meaning
7:1
0000000 Reserved
0
Power good
polarity of pin 12
0
Negative logic, output low if Vout rises to
specific value
1
Positive logic, output high if Vout rises to
specific value
CTRL/CS Pin
--
CTRL
CTRL
VOUT_DROOP TON_DELAY TOFF_DELAY TON_RISE TOFF_FALL
--
--
--
--
--
configurable configurable configurable configurable configurable
locked to 0x000A locked to 0x0001 locked to 0x0000 locked to 0x0000 locked to 0x0000
E8h: MFR_VIN_OV_FAULT_HYS
Hysteresis of VIN_OV_FAULT recover, Linear data format
E9h: MFR_VIN_UV_FAULT_HYS
Hysteresis of VIN_UV_FAULT recover, Linear data format
EAh: MFR_OT_FAULT_HYS
Hysteresis of OT_FAULT recover, Linear data format
F6h: MFR_CALIBRATION_STATUS
Refer to calibration procedure file
F9h: MFR_VIN_SENSE_CALIBRATION
Refer to calibration procedure file
FAh: MFR_IOUT_SENSE_CALIBRATION
Refer to calibration procedure file
FBh: MFR_VOUT_SET_POINT_CALIBRATION
Refer to calibration procedure file
FCh: MFR_SUPERVISOR_PASSWORD
Set unit to supervisor mode or ROM mode, Refer to password table
www.murata-ps.com/support