Series ZSE40/ISE40
Calibration Procedures
Auto Preset (In the case of confirming the supply pressure)
1. Auto preset mode
2. Preparation for auto preset
3. Auto preset of OUT1
SET
Press the “SET” button.
Select the Auto preset mode in
the initial setting mode and
press the “SET” button until
“ ” is displayed.
Prepare the equipment for use
under operating conditions.
When setting OUT1 is not
required, press both the į
button and Ĭ button
simultaneously in this state to
skip to “ ”.
4. Preparation for auto preset
The pressure is read and the
optimal set value is determind
automatically.
5. Auto preset of OUT2
SET
Press the “SET” button.
SET
Press the “SET” button.
SET
Press the “SET” button
to complete the setting.
ON point (C, C1)
OFF
Hysteresis (3 digits)
ON point = C, C1
OFF point = C-3 digits, C1-3 digits
(1 digit is the minimum setting unit.)
Other Functions
Prepare the equipment for use
under operating conditions of
OUT2.
When setting OUT2 is not
required, press both the į
button and Ĭ button
simultaneously in this state to
skip to the measurement mode.
The pressure is read and the
optimal set value is determind
automatically.
Ȝ Key lock mode
Used to avoid a malfunction when buttons on the front part of the switch are pressed.
Initiate key lock
Release key lock
SET
Press the “SET” button
to complete the setting.
SET
Press the “SET” button
to complete the setting.
Press the “SET” button for 4
seconds or longer.
Release it when the display
turns to “ ”.
Display “ ” by pressing į
button or Ĭ button.
Ȝ Peak mode
Allows holding of the maximum pressure
value on display under measurement.
While displayed, pressing the į button for 1
second or longer causes the peak mode to
display and blink.
Pressing the į button once again for 1 second
or longer reinstates it.
Note) Displaying the peak and the bottom
display is not distinguished.
Ȝ Zero clear
Allows an adjust to zero on the display
if the pressure to be measured is
within a range of ±70 digits from the
atmospheric pressure.
Pressing the į + Ĭ buttons simultaneously
with the supply pressure released to the
atmosphere, causes it to reset to zero on the
display and completes the zero clear
operation. The function then returns to the
measurement mode.
Press the “SET” button for 4
seconds or longer.
Release it when the display
turns to “ ”.
Display “ ” by pressing į
button or Ĭ button.
Ȝ Bottom mode
Allows holding of the minimum pressure
value on display under measurement.
While displayed, pressing the Ĭ button for 1
second or longer causes the bottom mode to
display and blink.
Pressing the Ĭ button once again for 1 second
or longer reinstates it.
Note) Displaying the peak and the bottom
display is not distinguished.