English
Language : 

PIC480.241C Datasheet, PDF (9/21 Pages) PULS GmbH – 24V, 20A, SINGLE PHASE INPUT
PIANO-Series
PRELIMINARY
PIC480.241C
24V, 20A, SINGLE PHASE INPUT
11. FUNCTIONAL DIAGRAM
Fig. 11-1 Functional diagram
L
Input Fuse
N
Input Filter
Input Rectifier
PFC
Converter
Power
Converter
Output
Filter
Inrush Current Limiter
DC-ok
Relay
Temper-
ature
Shut-
down
Output
Over-
Voltage
Protection
Output
Voltage
Regulator
+
+
-
-
DC-ok
Contact
DC-ok
LED
VOUT
12. TERMINALS AND WIRING
The terminals are IP20 finger safe constructed and suitable for field- and factory wiring.
Type
Solid wire
Stranded wire
American Wire Gauge
Maximal wire diameter
Wire stripping length
Screwdriver
Recommended tightening torque
Input and output
Screw terminals
max. 6mm2
max. 4mm2
AWG20-10
2.8mm (including ferrules)
7mm / 0.28inch
3.5mm slotted or cross-head No 2
1Nm, 9lb.in
DC-OK-Signal
Push-in terminals
max. 1.5mm2
max. 1.5mm2
AWG28-16
1.6mm (including ferrules)
7mm / 0.28inch
not required
not applicable
Instructions:
a) Use appropriate copper cables that are designed for minimum operating temperatures of:
75°C for ambient up to 55°C and
90°C for ambient up to 70°C minimum.
b) Follow national installation codes and installation regulations!
c) Ensure that all strands of a stranded wire enter the terminal connection!
d) Do not use the unit without PE connection.
e) Unused terminal compartments should be securely tightened.
f) Ferrules are allowed.
Jun. 2016 / Rev. 0.2 DS-PIC480.241C-EN
All parameters are specified at 24V, 20A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany