PIC480.241C Datasheet, PDF (8/21 Pages) PULS GmbH – 24V, 20A, SINGLE PHASE INPUT
PIANO-Series
PRELIMINARY
PIC480.241C
24V, 20A, SINGLE PHASE INPUT
9. EFFICIENCY AND POWER LOSSES
Efficiency
typ.
95.7%
at 24V, 20A, 230Vac
Average efficiency*)
typ.
95.2%
25% at 5A, 25% at 10A, 25% at 15A. 25% at 20A
Power losses
typ.
1.35W
at 24V, 0A, 230Vac
typ.
10.7W
at 24V, 10A, 230Vac
typ.
21.6W
at 24V, 20A, 230Vac
*) The average efficiency is an assumption for a typical application, where the power supply is loaded with 25% of the nominal load for
25% of the time, 50% of the nominal load for another 25% of the time, 75% of the nominal load for another 25% of the time and with
100% of the nominal load for the rest of the time.
Fig. 9-1 Efficiency vs. output current at 24V,
typ.
Efficiency
97%
96
95
94
93
92
91
Output Current
4 6 8 10 12 14 16 18 20A
Fig. 9-2 Losses vs. output current at 24V, typ.
Power Losses
24W
20
16
12
8
4
Output Current
0
0 2 4 6 8 10 12 14 16 18 20A
10. LIFETIME EXPECTANCY AND MTBF
Lifetime expectancy*)
93 000h
at 24V, 10A and 40°C, 230Vac
264 000h*)
at 24V, 10A and 25°C, 230Vac
51 000h
at 24V, 20A and 40°C, 230Vac
144 000h*)
at 24V, 20A and 25°C, 230Vac
MTBF**) SN 29500, IEC 61709
T.B.D.
at 24V, 20A and 40°C, 230Vac
T.B.D.
at 24V, 20A and 25°C, 230Vac
MTBF**) MIL HDBK 217F
T.B.D.
at 24V, 20A and 40°C, 230Vac;
Ground Benign GB40
T.B.D.
at 24V, 20A and 25°C, 230Vac;
Ground Benign GB25
T.B.D.
at 24V, 20A and 40°C, 230Vac;
Ground Fixed GF40
T.B.D.
at 24V, 20A and 25°C, 230Vac;
Ground Fixed GF25
*) The Lifetime expectancy shown in the table indicates the minimum operating hours (service life) and is determined by the lifetime
expectancy of the built-in electrolytic capacitors. Lifetime expectancy is specified in operational hours and is calculated according to the
capacitor’s manufacturer specification. The manufacturer of the electrolytic capacitors only guarantees a maximum life of up to 15 years
(131 400h). Any number exceeding this value is a calculated theoretical lifetime which can be used to compare devices.
**) MTBF stands for Mean Time Between Failure, which is calculated according to statistical device failures, and indicates reliability of a
device. It is the statistical representation of the likelihood of a unit to fail and does not necessarily represent the life of a product.
The MTBF figure is a statistical representation of the likelihood of a device to fail. A MTBF figure of e.g. 1 000 000h means that
statistically one unit will fail every 100 hours if 10 000 units are installed in the field. However, it can not be determined if the failed unit
has been running for 50 000h or only for 100h.
Jun. 2016 / Rev. 0.2 DS-PIC480.241C-EN
All parameters are specified at 24V, 20A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
8/21