English
Language : 

PIC480.241C Datasheet, PDF (11/21 Pages) PULS GmbH – 24V, 20A, SINGLE PHASE INPUT
PIANO-Series
PRELIMINARY
PIC480.241C
24V, 20A, SINGLE PHASE INPUT
14. EMC
The power supply is suitable for applications in industrial environment.
A detailed EMC report is available on request.
EMC Immunity
According generic standards: EN 61000-6-1 and EN 61000-6-2
Electrostatic discharge
EN 61000-4-2
contact discharge
air discharge
8kV
Criterion A
8kV
Criterion A
Electromagnetic RF field
EN 61000-4-3
80MHz-2.7GHz
10V/m
Criterion A
Fast transients (Burst)
Surge voltage on input
EN 61000-4-4
EN 61000-4-5
input lines
4kV
output lines
2kV
DC-OK signal (coupling clamp) 2kV
LÆN
2kV
L Æ PE, N Æ PE
4kV
Criterion A
Criterion A
Criterion A
Criterion A
Criterion A
Surge voltage on output
EN 61000-4-5
+Æ-
+ / - Æ PE
500V
1kV
Criterion A
Criterion A
Surge voltage on DC-OK
EN 61000-4-5
DC-OK signal Æ PE
1kV
Criterion A
Conducted disturbance
EN 61000-4-6
0.15-80MHz
10V
Criterion A
Mains voltage dips
EN 61000-4-11
0% of 200Vac
40% of 200Vac
70% of 200Vac
0Vac, 20ms
80Vac, 200ms
140Vac, 500ms
Criterion A
Criterion C
Criterion C
Voltage interruptions
EN 61000-4-11
0% of 200Vac (=0V)
5000ms
Criterion C
Voltage sags
SEMI F47 0706
dips on the input voltage according to SEMI F47 standard
80% of 200Vac (160Vac)
70% of 200Vac (140Vac)
50% of 200Vac (100Vac)
1000ms
500ms
200ms
Criterion A
Criterion C
Criterion C
Powerful transients
VDE 0160
over entire load range
750V, 0.3ms
Criterion A
Criterions:
A: Power supply shows normal operation behavior within the defined limits.
B: Temporary voltage dips possible. No change in operation mode.
C: Temporary loss of function is possible. Power supply may shut-down and restarts by itself. No damage or hazards for the power supply
will occur.
EMC Emission
According generic standards: EN 61000-6-3, EN 61000-6-4
Conducted emission
input lines
EN 55011, EN 55022, FCC Part 15,
CISPR 11, CISPR 22
Class B fulfilled
Conducted emission
output lines**)
IEC/CISPR 16-1-2, IEC/CISPR 16-2-1
limits for DC power port according EN
61000-6-3 not fulfilled
Radiated emission
EN 55011, EN 55022
Class B fulfilled
Harmonic input current
EN 61000-3-2
Class A fulfilled between 0A and 20A load
Class C fulfilled between 7A and 20A load
Voltage fluctuations,
flicker
EN 61000-3-3
fulfilled*)
This device complies with FCC Part 15 rules.
Operation is subjected to following two conditions: (1) this device may not cause harmful interference, and (2) this
device must accept any interference received, including interference that may cause undesired operation.
*) tested with constant current loads, non pulsing
**) for information only, not mandatory for EN 61000-6-3
Switching Frequencies
Switching frequency 1
Switching frequency 2
The power supply has two converters with two different switching frequencies included.
40-120kHz
PFC converter, input voltage and output power dependent
80-140kHz
Main converter, output voltage and output power dependent
Jun. 2016 / Rev. 0.2 DS-PIC480.241C-EN
All parameters are specified at 24V, 20A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
11/21