PIC480.241C Datasheet, PDF (4/21 Pages) PULS GmbH – 24V, 20A, SINGLE PHASE INPUT
PIANO-Series
PRELIMINARY
PIC480.241C
24V, 20A, SINGLE PHASE INPUT
3. AC-INPUT
AC input
AC input range
Allowed voltage L or N to earth
Input frequency
Turn-on voltage
Shut-down voltage
External input protection
nom.
AC 200-240V suitable for TN-, TT- and IT mains networks
min.
180-264Vac
continuous operation
min.
264-300Vac
< 500ms
max.
300Vac
continuous, IEC 62103
nom.
50–60Hz
±6%
typ.
152Vac
steady-state value, see Fig. 3-1
typ.
142Vac
steady-state value, see Fig. 3-1
See recommendations in chapter 23.3.
Input current
typ.
2.2A
at 24V, 20A, 230Vac, see Fig. 3-3
Power factor*)
typ.
0.99
at 24V, 20A, 230Vac, see Fig. 3-4
Crest factor**)
typ.
1.6
at 24V, 20A, 230Vac
Start-up delay
typ.
400ms
see Fig. 3-2
Rise time
typ.
60ms
at 24V, 20A const. current load, 0mF load capacitance,
see Fig. 3-2
typ.
240ms
at 24V, 20A const. current load, 20mF load capacitance,
see Fig. 3-2
Turn-on overshoot
max.
200mV
resistive load, see Fig. 3-2
*) The power factor is the ratio of the true (or real) power to the apparent power in an AC circuit.
**) The crest factor is the mathematical ratio of the peak value to RMS value of the input current waveform.
Fig. 3-1 Input voltage range, typ.
POUT
Rated
input range max.
500ms
Fig. 3-2 Turn-on behavior, definitions
Input
Voltage
180V
VIN
264V 300Vac
Fig. 3-3 Input current vs. output load at 24V
Input Current, typ.
3A
2.5
2.0
1.5
1.0
0.5
Output Current
0
0 2 4 6 8 10 12 14 16 18 20A
Output
Voltage
- 5%
Start-up Rise
delay Time
Fig. 3-4 Power factor vs. output load
Power Factor, typ.
1.00
0.98
0.96
0.94
0.92
0.90
0.88
Output Current
2 4 6 8 10 12 14 16 18 20A
Jun. 2016 / Rev. 0.2 DS-PIC480.241C-EN
All parameters are specified at 24V, 20A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
4/21