English
Language : 

PIC480.241C Datasheet, PDF (13/21 Pages) PULS GmbH – 24V, 20A, SINGLE PHASE INPUT
PIANO-Series
PRELIMINARY
PIC480.241C
24V, 20A, SINGLE PHASE INPUT
16. PROTECTION FEATURES
Output protection
Electronically protected against overload, no-load and short-circuits*)
Output over-voltage protection typ. 30.5Vdc
max. 32.0Vdc
In case of an internal power supply defect, a redundant
circuit limits the maximum output voltage. The output
shuts down and automatically attempts to restart.
Degree of protection
IP 20
EN/IEC 60529
Caution: For use in a controlled environment according
to CSA 22.2 No 107.1-01.
Over-temperature protection
yes
Output shut-down with automatic restart
Input transient protection
MOV (Metal Oxide Varistor)
Internal input fuse
included
not user replaceable
*) In case of a protection event, audible noise may occur.
17. SAFETY FEATURES
Input / output separation
Class of protection
Isolation resistance
Touch current (leakage current)
SELV
IEC/EN 60950-1
PELV
IEC/EN 60204-1, EN 50178, IEC 62103, IEC 60364-4-41
double or reinforced insulation
I
PE (Protective Earth) connection required
> 5MOhm
input to output, 500Vdc
0.33mA / 0.69mA
230Vac, 50Hz, TN-,TT-mains / IT-mains
0.43mA / 0.89mA
264Vac, 50Hz, TN-,TT-mains / IT-mains
Jun. 2016 / Rev. 0.2 DS-PIC480.241C-EN
All parameters are specified at 24V, 20A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
13/21