CP10.121 Datasheet, PDF (6/26 Pages) PULS GmbH – SINGLE PHASE INPUT
CP-Series
CP10.121
12V, 16A, SINGLE PHASE INPUT
6. OUTPUT
Output voltage
nom. 12V
Adjustment range
min. 12-15V
guaranteed
max. 16.5V****)
at clockwise end position of potentiometer
Factory settings
typ. 12.0V
±0.2%, at full load and cold unit
Line regulation
Load regulation
max.
max.
10mV
50mV
85-300Vac
static value, 0A Æ 16A; see Fig. 6-1
Ripple and noise voltage
max. 50mVpp
20Hz to 20MHz, 50Ohm
Output current
nom. 16A
at 12V, ambient temperature <60°C, see Fig. 6-1
nom. 19.2A*)
at 12V, ambient temperature <45°C, see Fig. 16-1
nom. 12A
at 12V and 70°C ambient temperature, see Fig. 16-1
nom. 12.8A
at 15V, ambient temperature <60°C, see Fig. 6-1
nom. 15.4A*)
at 15V, ambient temperature <45°C, see Fig. 16-1
nom. 9.6A
at 15V and 70°C ambient temperature, see Fig. 16-1
typ. 48A
up to at least 12ms*****), output voltage stays above
10V, see Fig. 6-2 and Fig. 24-3, This peak current is
available once every five seconds (hardware
controlled).
Output power
nom. 192W
continuously available
nom. 230W*)
Power Boost® *)
Overload behaviour
cont. current
output voltage > 6.5Vdc, see Fig. 6-1
HiccupPLUS mode**) output voltage < 6.5Vdc, see Fig. 6-1
Short-circuit current
min.
22.5A***)
load impedance <30mOhm, see Fig. 6-3
max. 27.5A***)
load impedance <30mOhm, see Fig. 6-3
max. 7.9A
average (R.M.S.) current, load impedance 50mOhm,
see Fig. 6-3
min. 50A
up to 12ms, load impedance <30mOhm, see Fig. 6-2
typ. 55A
up to 12ms, load impedance <30mOhm, see Fig. 6-2
Output capacitance
typ. 5 350μF
included inside the power supply
*)
Power Boost
This power/ current is continuously allowed up to an ambient temperature of 45°C.
Above 45°C, do not use this power/ current longer than a duty cycle of 10% and/ or not longer than 1 minute every 10 minutes.
**) HiccupPLUS Mode
At heavy overloads (when output voltage falls below 6.5V), the power supply delivers continuous output current for 2s. After this, the
output is switched off for approx. 18s before a new start attempt is automatically performed. This cycle is repeated as long as the
overload exists. If the overload has been cleared, the device will operate normally. See Fig. 6-3
***) Discharge current of output capacitors is not included.
****) This is the maximum output voltage which can occur at the clockwise end position of the potentiometer due to tolerances. It is not a
guaranteed value which can be achieved. The typical value is about 15.5V.
*****) Reduced pulse length for AC 100V mains.
Feb. 2016 / Rev. 1.1 DS-CP10.121-EN
All parameters are specified at 12V, 16A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
6/26