CP10.121 Datasheet, PDF (14/26 Pages) PULS GmbH – SINGLE PHASE INPUT
CP-Series
CP10.121
12V, 16A, SINGLE PHASE INPUT
Switching Frequencies
Switching frequency 1
Switching frequency 2
Switching frequency 3
The power supply has three converters with two different switching frequencies included.
110kHz
PFC converter, input voltage and output power dependent
110kHz to 140kHz
Main converter, output power dependent
60kHz
Auxiliary converter
16. ENVIRONMENT
Operational temperature*) -25°C to +70°C (-13°F to 158°F)
reduce output power according Fig. 16-1
Storage temperature
-40°C to +85°C (-40°F to 185°F)
for storage and transportation
Output de-rating
2.5W/°C
4.8W/°C
45°C to 60°C (113°F to 140°F)
60°C to 70°C (140°F to 158°F)
Humidity**)
5 to 95% r.h.
IEC 60068-2-30
Vibration sinusoidal
2-17.8Hz: ±1.6mm; 17.8-500Hz: 2g***)
2 hours / axis***)
IEC 60068-2-6
Shock
30g 6ms, 20g 11ms***)
IEC 60068-2-27
3 bumps / direction, 18 bumps in total
Altitude
0 to 2000m (0 to 6 560ft)
without any restrictions
2000 to 6000m (6 560 to 20 000ft)
reduce output power or ambient temperature,
see Fig. 16-2.
IEC 62103, EN 50178, overvoltage category II
Altitude de-rating
13.5W/1000m or 5°C/1000m
> 2000m (6500ft), see Fig. 16-2
Over-voltage category
III
IEC 62103, EN 50178, altitudes up to 2000m
II
altitudes from 2000m to 6000m
Degree of pollution
2
IEC 62103, EN 50178, not conductive
LABS compatibility
The unit does not release any silicone or other LABS-critical substances and is suitable for
use in paint shops.
*) Operational temperature is the same as the ambient or surrounding temperature and is defined as the air temperature 2cm below the
unit.
**) Do not energize while condensation is present
***) Tested in combination with DIN-Rails according to EN 60715 with a height of 15mm and a thickness of 1.3mm and standard
orientation.
Fig. 16-1 Output current vs. ambient temp.
Allowed Output Current at 12V
20A
B
A
16A
12A
8A
4A
0
-25
A... 85 to 264Vac, continuous
B... short term
0
20 40 60 70°C
Ambient Temperature
Fig. 16-2 Output current vs. altitude
Allowed Output Current at 12V
20A
D
16A
C
B
A
12A
8A
4A
0
0
A... Tamb < 60°C
B... Tamb < 50°C
C... Tamb < 40°C
D... Short term
2000m 4000m
6000m
Altitude
Feb. 2016 / Rev. 1.1 DS-CP10.121-EN
All parameters are specified at 12V, 16A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
14/26