English
Language : 

CP10.121 Datasheet, PDF (4/26 Pages) PULS GmbH – SINGLE PHASE INPUT
CP-Series
CP10.121
12V, 16A, SINGLE PHASE INPUT
3. AC-INPUT
AC input
AC input range
Allowed voltage L or N to earth
Input frequency
Turn-on voltage
Shut-down voltage
External input protection
nom. AC 100-240V
suitable for TN-, TT- and IT mains networks
min. 85-264Vac
continuous operation
min. 264-300Vac
< 500ms
max. 300Vac
continuous, IEC 62103
nom. 50–60Hz
±6%
typ. 80Vac
steady-state value, see Fig. 3-1
typ. 55Vac
dynamic value (250ms)
typ. 70Vac
steady-state value, see Fig. 3-1
See recommendations in chapter 24.3.
AC 100V AC 120V AC 230V
Input current
typ.
2.11A
1.74A
0.92A at 12V, 16A, see Fig. 3-3
Power factor*)
typ.
0.99
0.99
0.96
at 12V, 16A, see Fig. 3-4
Crest factor**)
typ.
1.5
1.5
1.65
at 12V, 16A
Start-up delay
typ.
300ms
290ms
240ms see Fig. 3-2
Rise time
typ.
18ms
18ms
18ms
at 12V, 16A const. current load,
0mF load capacitance, see Fig. 3-2
typ.
35ms
35ms
35ms
at 12V, 16A const. current load,
16mF load capacitance,, see Fig. 3-2
Turn-on overshoot
max.
200mV
200mV
200mV see Fig. 3-2
External input protection
See recommendations in chapter 24.3.
*) The power factor is the ratio of the true (or real) power to the apparent power in an AC circuit.
**) The crest factor is the mathematical ratio of the peak value to RMS value of the input current waveform.
POUT
Fig. 3-1 Input voltage range
Rated
input range
max.
500ms
Fig. 3-2 Turn-on behavior, definitions
Input
Voltage
VIN
85V
264V 300Vac
Fig. 3-3 Input current vs. output current at
12V output voltage
Input Current, typ.
3A
2.5
a) 100Vac
(a)
2.0
b) 120Vac
c) 230Vac
(b)
1.5
1.0
(c)
0.5
Output Current
0
0 2 4 6 8 10 12 14 16 18 20A
Output
Voltage
- 5%
Start-up Rise
delay Time
Fig. 3-4 Power factor vs. output current at
12V output voltage
Power Factor, typ.
1.0
0.95 (a)
(b)
0.9
0.85
(c)
0.8
0.75
2468
10 12
(a) 100Vac,
(b) 120Vac,
(c) 230Vac
Output Current
14 16 18 20A
Feb. 2016 / Rev. 1.1 DS-CP10.121-EN
All parameters are specified at 12V, 16A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
4/26