CP10.121 Datasheet, PDF (5/26 Pages) PULS GmbH – SINGLE PHASE INPUT
CP-Series
CP10.121
12V, 16A, SINGLE PHASE INPUT
4. DC-INPUT
DC input
DC input range
DC input current
Allowed Voltage L/N to Earth
Turn-on voltage
Shut-down voltage
nom.
min.
typ.
max.
typ.
typ.
DC 110-150V
88-187Vdc
1.9A
375Vdc
80Vdc
70Vdc
±20%
continuous operation
110Vdc, at 12V, 16A
continuous, IEC 62103
steady state value
steady state value
Fig. 4-1 Wiring for DC Input
Battery
Power Supply
+
AC
L
N
+
PE
-
Load
Instructions for DC use:
a) Use a battery or a similar DC source. A supply from the
intermediate DC-bus of a frequency converter is not
recommended and can cause a malfunction or damage
the unit.
b) Connect +pole to L and –pole to N.
c) Connect the PE terminal to an earth wire or to the
machine ground.
-
DC
5. INPUT INRUSH CURRENT
An active inrush limitation circuit (NTCs, which are bypassed by a relay contact) limits the input inrush current after
turn-on of the input voltage.
The charging current into EMI suppression capacitors is disregarded in the first microseconds after switch-on.
Inrush current
Inrush energy
max.
typ.
typ.
max.
AC 100V
11Apeak
9Apeak
9Apeak
0.1A²s
AC 120V
7Apeak
6Apeak
6Apeak
0.1A²s
AC 230V
11Apeak
6Apeak
9Apeak
0.4A²s
at 40°C, cold start
at 25°C, cold start
at 40°C, cold start
at 40°C, cold start
Fig. 5-1 Typical turn-on behaviour at nominal
load, 120Vac input and 25°C ambient
50ms/DIV
Input current
2A/DIV
Fig. 5-2 Typical turn-on behaviour at nominal
load, 230Vac input and 25°C ambient
6A
50ms/DIV
Input current
2A/DIV
Input voltage
6A
250V/DIV
Input voltage
500V/DIV
Output voltage 10V/DIV
Output voltage 10V/DIV
Feb. 2016 / Rev. 1.1 DS-CP10.121-EN
All parameters are specified at 12V, 16A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
5/26