13. TERMINALS AND WIRING
The terminals are IP20 finger safe constructed and suitable for field- and factory wiring.
Type
Solid wire
Stranded wire
American Wire Gauge
Wire diameter
Wire stripping length
Screwdriver
Recommended tightening torque
Input and output
screw terminals
max. 6mm2
max. 4mm2
AWG20-10
max. 2.8mm (including ferrules)
7mm / 0.28inch
3.5mm slotted or cross-head No 2
1Nm, 9lb.in
DC-OK-Signal, Shut-down input
push-in terminals
max. 1.5mm2
max. 1.5mm2
AWG28-16
max. 1.6mm (including ferrules)
7mm / 0.28inch
not required
not applicable
Instructions:
a) Use appropriate copper cables that are designed for minimum operating temperatures of:
60°C for ambient up to 45°C and
75°C for ambient up to 60°C minimum
90°C for ambient up to 70°C minimum.
b) Follow national installation codes and installation regulations!
c) Ensure that all strands of a stranded wire enter the terminal connection!
d) Do not use the unit without PE connection.
e) Unused terminal compartments should be securely tightened.
f) Ferrules are allowed.
Daisy chaining:
Daisy chaining (jumping from one power supply output to the next) is allowed as long as the average output current
through one terminal pin does not exceed 25A. If the current is higher, use a separate distribution terminal block as
shown in Fig. 13-2.
Fig. 13-1 Daisy chaining of outputs
Power
Supply
++- -
Output
Power
Supply
++- -
Output
max 25A!
continuous
Load
+-
Fig. 13-2 Using distribution terminals
Power
Supply
+ +- -
Output
Power
Supply
+ +- -
Output
Distribution
Terminals
Load
+-
Feb. 2016 / Rev. 1.1 DS-CP10.121-EN
All parameters are specified at 12V, 16A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.