English
Language : 

S8VS-03024 Datasheet, PDF (6/38 Pages) Omron Electronics LLC – Switch Mode Power Supply
S8VS
Power ratings
120 W
180 W
Item
Type
Standard
Maintenance
forecast monitor
Total run time
monitor
Standard
Maintenance
forecast monitor
Total run time
monitor
Efficiency
With 100-VAC input 84% typical
With 200-VAC input 87% typical
83% typical
85% typical
85% typical
88% typical
85% typical
87% typical
Voltage *1
100 to 240 VAC (allowable range: 85 to 264 VAC or 80 to 370 VDC *11)
Frequency *1
50/60 Hz (47 to 63 Hz)
Current
With 100-VAC input
With 200-VAC input
1.9 A max., 1.5 A typical
1.1 A max.,
0.71 A typical
1.1 A max., 0.72 A typical
2.9 A max., 2.2 A typical
1.6 A max., 1.1 A typical
Input
Power factor
Harmonic current regulation
0.9 min.
Conforms to EN61000-3-2
Leakage current
With 100-VAC input 0.5 mA max.
With 200-VAC input 1.0 mA max.
Inrush current *2
With 100-VAC input 17.5 A max., 14 A typical
With 200-VAC input 35 A max., 28 A typical
Voltage adjustment range *3
−10% to 15% (with V.ADJ)
Ripple noise voltage (at rated I/O)
60 mV max.
130 mV max.
50 mV max.
180 mV max.
Input variation influence
0.5% max. (at 85- to 264-VAC input, 100% load)
Output
Load variation influence
(rated input voltage)
Temperature variation influence
1.5% max. (with rated input, 0 to 100% load)
0.05%/°C max.
Startup time
(at rated I/O) *2
With 100-VAC input 550 ms typical
With 200-VAC input 400 ms typical
650 ms typical
520 ms typical
570 ms typical
470 ms typical
580 ms typical
490 ms typical
Output hold time
(at rated I/O) *2
With 100-VAC input 52 ms typical
With 200-VAC input 54 ms typical
56 ms typical
56 ms typical
58 ms typical
62 ms typical
70 ms typical
70 ms typical
Overload protection *2
105% to 160% of rated load current, inverted L voltage drop, automatic reset
Overvoltage protection *2, *4
Yes
Output voltage indication *5
No
Yes (selectable) *6
No
Yes (selectable) *6
Output current indication *5
No
Yes (selectable) *7
No
Yes (selectable) *7
Peak-hold current indication *5
No
Yes (selectable) *8
No
Yes (selectable) *8
Maintenance forecast monitor indication *5 No
Yes (selectable) No
No
Yes (selectable) No
Maintenance forecast monitor output
No
Additional
functions Total run time monitor indication *5
No
Yes (transistor
output), 30 VDC
max., 50 mA max.
No
No
*9
Yes (selectable) No
Yes (transistor
output), 30 VDC
max., 50 mA max.
*9
No
Yes (selectable)
Total run time monitor output *5
No
Yes (transistor
output), 30 VDC
max., 50 mA max.
No
*9
Yes (transistor
output), 30 VDC
max., 50 mA max.
*9
Undervoltage alarm indication *5
No
Yes (selectable)
No
Yes (selectable)
Undervoltage alarm output terminals
No
Yes (transistor output), 30 VDC max.,
50 mA max. *9
No
Yes (transistor output), 30 VDC max.,
50 mA max. *9
Parallel operation
No
Series operation
Yes for up to 2 Power Supplies (with external diode)
Operating ambient temperature
Refer to the derating curve in . (with no icing or condensation)
Storage temperature
−25 to 65°C
Operating ambient humidity
25% to 85% (Storage humidity: 25% to 90%)
Dielectric strength
3.0 kVAC for 1 min. (between all inputs and outputs/ alarm outputs; detection current: 20 mA)
2.0 kVAC for 1 min. (between all inputs and PE terminals; detection current: 20 mA)
1.0 kVAC for 1 min. (between all outputs/ alarm outputs and PE terminals; detection current for standard models: 30 mA, detection
current for models with indication monitor: 20 mA
500 VAC for 1 min. (between all outputs and alarm outputs; detection current: 20 mA)
Insulation resistance
100 MΩ min. (between all outputs/ alarm outputs and all inputs/ PE terminals) at 500 VDC
Vibration resistance
10 to 55 Hz, 0.375-mm single amplitude for 2 h each in X, Y, and Z directions
10 to 150 Hz, 0.35-mm single amplitude (5 G max.) for 80 min each in X, Y, and Z directions
Shock resistance
150 m/s2, 3 times each in ±X, ±Y, and ±Z directions
Other
Output indicator
EMI
Yes (color: green)
Conducted
Emissions
Models with indication monitor: Conforms to EN61204-3 EN55011 Class A and based on FCC Class A, Conforms to EN61204-3
EN55011 Class B *11
Standard models: Conforms to EN61204-3 EN55011 Group 1 Class B and based on FCC Class A
Radiated Emissions
Models with indication monitor: Conforms to EN61204-3 EN55011 Class A, Conforms to EN61204-3 EN55011 Class B *11
Standard models: Conforms to EN61204-3 EN55011 Group 1 Class B
EMS
Conforms to EN61204-3 high severity levels
Approved standards *11
UL Listed: UL 508 (Listing),
UL UR: UL 60950-1 (Recognition),
cUL: CSA C22.2 No. 107.1,
cUR: CSA C22.2 No. 60950-1,
EN/VDE: EN 50178 (= VDE 0160), EN 60950-1 (= VDE 0805 Teil 1)
KOSHA S Mark *10
SEMI *11
F47-0706 (200-VAC input)
Weight
550 g max.
850 g max.
Note: Refer to page 5 for notes 1 to 11.
6