English
Language : 

S8VS-03024 Datasheet, PDF (18/38 Pages) Omron Electronics LLC – Switch Mode Power Supply
S8VS
Engineering Data
Derating Curve
15 W <S8VS-015@@>
120
100
1
80
*1
60
*2
40
*3
20
0
−20 −10 0
10 20 30 40 50 60 70 80
Ambient temperature (°C)
*1 Standard mounting
*2 Face-up mounting
*3 Horizontal mounting
30 W <S8VS-03005/S8VS-03012>
120
100
1
80
*1
60
*2
40
20
0
−20 −10 0 10 20 30 40 50 60 70 80
Ambient temperature (°C)
*1 Standard mounting
*2 Face-up mounting/Horizontal mounting
30 W <S8VS-03024>
120
100
1
80
*1
60
*2
40
20
0
−20 −10 0
10 20 30 40 50 60 70 80
Ambient temperature (°C)
*1 Standard mounting
*2 Face-up mounting/Horizontal mounting
Note: 1. Internal parts may occasionally deteriorate or be damaged.
Do not use the Power Supply in areas outside the derating
curve (i.e., the area shown by shading A in the above
graph).
2. If there is a derating problem, use forced air-cooling.
3. Provide a space of at least 20 mm when using standard
mounting and horizontal mounting. If 20 mm is not available,
make sure that the space is at least 10 mm. In this case,
reduce the corresponding derating curve by 5°C.
4. DC Inputs
If the input voltage is less than 100 VDC, reduce the load
given in the above derating curve by at least the following
factor.
S8VS-03005: 0.7 max.
S8VS-03012/03024: 0.85 max.
18
60, 90, 120, 180, 240, and 480 W
120
1
100
*
80
60
40
20
0
−20 −10 0 10 20 30 40 50 60 70 80
Ambient temperature (°C)
* Using side mounting bracket for right-side mounting (excluding
240-W models). UL certification conditions do not apply if the side
mounting bracket is used.
Note: 1. Internal parts may occasionally deteriorate or be damaged.
Do not use the Power Supply in areas outside the derating
curve (i.e., the area shown by shading A in the above
graph).
2. If there is a derating problem, use forced air-cooling.
3. When using a 480-W model at an input voltage of 95 VAC
or less, derate the load by at least 80%.
4. DC Inputs
If the input voltage is less than 100 VDC, reduce the load
given in the above derating curve by at least the following
factor.
60-W models: 0.9 max.
90-W models: 0.85 max.
120-W/180-W/240-W models: 0.8 max.