Outputs
Comparative Output Pattern out-p R P C
Standard, zone, and level comparative output patterns can be
selected for comparative outputs.
Hysteresis
hys R
Prevents comparative outputs from chattering when the
measurement value fluctuates slightly near the set value.
Output Refresh Stop o-stp R P
Holds the output status when a comparative result output other than
PASS turns ON.
PASS Output Change pass R P
Comparative results other than PASS and error signals can be
output from the PASS output terminal.
Output OFF Delay
off-d R P C
Delays turning OFF comparatives for a set period. This can be used
to provide sufficient time to read the comparative output ON status
when the comparative result changes at short intervals.
Shot Output
shot R P C
Turns ON the comparative output for a specific time.
Output Logic
out-n R P C
Reverses the output logic of comparative results.
Startup Compensation Timer s-tmr R
Measurements can be stopped for a set time using an external input.
Output Test
test R P C
Output operation can be checked without using actual input signals
by using the keys to set a test measurement value.
Linear Outputs
lset.c, lset.v, lset.h, lset.l
RPC
A current or voltage proportional to the change in the measurement
value can be output.
Standby Sequence stdby R P
The comparison outputs can be kept OFF until the measurement
value enters the PASS range.
Display
Display Value Selection disp R P C
The display value can be set to the present value, the maximum
value, or the minimum value.
Display Color Selection color R P C
The present value display color can be set to green or red. The color
of the present value can also be switched according to the
comparative output.
Display Refresh Period d.ref R P C
When the input changes rapidly, the display refresh period can be
lengthened to control flickering and make the display easier to read.
Position Meter
pos-t, pos-h, pos-l
RPC
The present measurement value can be displayed as a position in
relation to the scaling width on a 20-gradation position meter.
Prescale
ps.ax, ps.ay, ps.bx, ps.by
RPC
The input signal can be converted and displayed as any value.
Comparative Set Value Display sv.dsp R P C
Select whether or not to display the comparative value during
operation.
Display auto-return ret R P C
Automatically returns the display to RUN level when there are no key
operations (e.g., max./min. switching, bank settings using keys).
Other
Max./Min. Hold
RP
Holds the maximum and minimum measurement values.
Bank Selection
bnk-c R P C
Switch between 8 comparative value banks using the keys on the
front panel or external inputs. A set of set comparative values can be
selected as a group.
Bank Copy
copy R P C
Any bank settings can be copied to all banks.
Interruption Memory memo C
The measured value can be recorded when the power supply is
interrupted.
User Calibration
RPC
The K3HB can be calibrated by the user.
Digital Indicators K3HB-R/-P/-C
29