English
Language : 

705-5100-F21 Datasheet, PDF (32/52 Pages) Magnetrol International, Inc. – Enhanced Model 705 with PROFIBUS PA™ Digital Output
Display
16
SZHeight
xx.x su
17
SZ Latch
Reset
18
Threshld
(select)
19
Trim Lvl
xx.x su
Password
User
Action
Enter distance below BlockDis where
SZ Fault will be asserted
Comment
5.1 to 2286 cm (2 to 900 in)
User
Press Enter to clear a Safety Zone latch
User
Select from CFD, Fixed
Superuser or Enter value to adjust Level reading
user
For interface, refers to threshold for
upper level pulse
-20.0 inches <= Lvl Trim <= +20.0 inches
(Superuser password required if negative
fiducial.)
20
Dev Addr
User
Set Device Address
0 to 126
21
AIDisp
(select)
22
LvlTicks
xxxxx
23
New Pass
xxx
24
Language
(select)
25
Mdl705PA
Ver 3.0A
26
DispFact
(select)
27 History Status
(status)
28
Run Time
xxxx.x h
29
History
Reset
30
HF Cable
(select)
31
FidTicks
xxxx
32
Fid Sprd
xxx
User
User
User
User
None
None
None
None
Superuser
Superuser
None
None
33
Fid Type
(select)
Superuser
34 Fid Gain
xxx
35
Window
xxx
36 Conv Fct
xxxx
37 Scl Ofst
xxx
38 Neg Ampl
xxx
39 Pos Ampl
xxx
40
Signal
xxx
Superuser
Factory
Factory
Factory
Superuser
Superuser
None
Select AI Block Out values to be displayed
Diagnostic Display
Time of flight from fiducial to level signal
Enter new password (0-255)
Select from English, Spanish, French,
German
Transmitter Display
Select Yes to display factory parameter
menus
Diagnostic Display to view present status
and recent exceptions
Diagnostic Display showing elapsed
time since power on
Press Enter and select yes to clear
history
Displays encrypted value of present
password
Language choice for
LCD display
Product identification
Firmware version
Cleared to zero with History Reset
Similar to SZ Mode Reset.
Select length of remote extension cable Select Integral, 3-foot, 12-foot
Diagnostic Display
Time of flight from start of
ramp to fiducial
Diagnostic Display
Spread in fiducial ticks readings
Superuser parameter
Select from Positive, Negative.
Selection only allowed for some probes,
fixed for others
Superuser parameter
Factory Parameter
Calibration parameter
Factory Parameter
Calibration parameter
Factory Parameter
Calibration parameter
Superuser Parameter
Diagnostic parameter
Superuser Parameter
Diagnostic Display
Diagnostic parameter
Indication of level
signal amplitude
32
57-645 Eclipse Guided Wave Radar Transmitter - PROFIBUS PA™