705-5100-F21 Datasheet, PDF (31/52 Pages) Magnetrol International, Inc. – Enhanced Model 705 with PROFIBUS PA™ Digital Output
Display
*Status*
1
*Level*
*AI1Lvl*
2
Level
xxx.x lu
3
LvlUnits
(select)
4
AI1LVl
xx.x%
5
PrbModel
(select)
6
PrbMount
(select)
7
MeasType
(select)
8
SnsrUnit
(select)
9
Probe Ln
xxx.x su
10
PrbLvlUn
11
Lvl Ofst
xxx.x plu
12
Dielctrc
(select)
13
Senstvty
xxx
14
BlockDis
xx.x su
15
SftyZone
(select)
5.0 Model 705 Menu: Step by Step Procedures
Password
The following table describes the software menu displayed
by the Eclipse PROFIBUS PATM transmitter for “Level
Only” measurement. Use this table as a step by step guide
to configure the transmitter.
The second column presents the menus shown on the trans-
mitter display. The displays are in the order they would
appear if the arrow keys were used to scroll through the
menu. The numbers on the first column are not shown in
the display. They are only provided as reference.
The third column provides the actions to take when config-
uring the transmitter. Additional information or an explana-
tion of an action is given in the fourth coulmn. (Shaded
sections are factory menu items).
Action
Comment
None
Transmitter Display
MeasType = Lvl Only
None
Transmitter Display
All MeasType selections
User
Select the Level units
Select from cm, inches, feet, meters,
percent
None
Transmitter Display
All MeasType selections
User
Select the type of probe used
User
User
Select the type of probe
mounting
Select type of measurement
Select from 7xA-x, 7xB-x, 7xD-x,
7xG-x, 7xK-x, 7xP-x, 7xR-x, 7xE-x,
7xF-x, 7xF-E, 7xF-F, 7x1-x, 7x2-x,
7x5-x, 7x7-x, 7xF-4, 7xF-P, 7xJ-x,
7xL-x, 7xM-x, 7xN-x, 7xS-x, 7xT-x
Select from NPT, BSP or Flange
Select from Lvl Only, Lvl&Vol, Intrface,
Ifc&Vol
User
Select the Sensor units
Select from cm, inches, feet, meters
User
User
User
User
Superuser or
user
User
User
Enter the exact length
of the probe
11.8 to 900 in (30 to 2286 cm)
Select Probe Level units
Select from cm, inches, feet, meters,
percent
Enter desired Level reading when probe
is dry
-90 to 300 in (-228.6 to 762 cm)
Select range bounding the dielectric con- Select from 1.4-1.7, 1.7-3,
stant of the medium
3-10, 10-100
Adjust gain value upward or downward (Superuser password required for dual ele-
to sense liquid surface
ment probes.)
Enter distance below reference point
where level is not sensed
-99.9 to 2286 cm (-39.3 to 900 in)
Select behavior when level is sensed in
safety zone
Off, On, Latch
57-645 Eclipse Guided Wave Radar Transmitter - PROFIBUS PA™