English
Language : 

RHFAC244D03V Datasheet, PDF (11/27 Pages) List of Unclassifed Manufacturers – DLA LAND AND MARITIME COLUMBUS, OHIO 43218-3990
TABLE IA. Electrical performance characteristics - Continued.
4/ For negative and positive voltage and current values, the sign designates the potential difference in reference to GND
and the direction of current flow, respectively; and the absolute value of the magnitude, not the sign, is relative to the
minimum and maximum limits, as applicable, listed herein. All devices shall meet or exceed the limits specified in
table IA, as applicable, at 3.0 V ≤ VCC ≤ 3.6 V and 4.5 V ≤ VCC ≤ 5.5 V.
5/ The VOH and VOL tests shall be tested at VCC = 3.0 V and 4.5 V. The VOH and VOL tests are guaranteed, if not tested, for
other values of VCC. Limits shown apply to operation at VCC = 3.3 V ±0.3 V and VCC = 5.0 V ±0.5 V. Tests with input
current at +50 mA or -50 mA are performed on only one input at a time with duration not to exceed 10 ms. Transmission
driving tests may be performed using VIN = VCC or GND. When VIN = VCC or GND is used, the test is guaranteed for
VIN = VIH minimum and VIL maximum.
6/ The VIH and VIL tests are not required if applied as forcing functions for VOH and VOL tests.
7/ The maximum limit for this parameter at 100 krads (Si) is 4 µA.
8/ Power dissipation capacitance (CPD) determines both the dynamic power consumption (PD) and dynamic current
consumption (IS).
Where:
PD = (CPD + CL) (VCC x VCC)f + (ICC x VCC)
IS = (CPD + CL) VCCf + ICC
f is the frequency of the input signal and CL is the external output load capacitance.
9/ Tests shall be performed in sequence, attributes data only. Functional tests shall include the truth table and other logic
patterns used for fault detection. The test vectors used to verify the truth table shall, at a minimum, test all functions of
each input and output. All possible input to output logic patterns per function shall be guaranteed, if not tested, to the
truth table in figure 3 herein. Functional tests shall be performed in sequence as approved by the qualifying activity on
qualified devices. Allowable tolerances in accordance with MIL-STD-883 for the input voltage levels may be
incorporated. For VOUT measurements, L ≤ 0.3VCC and H ≥ 0.7VCC.
10/ AC limits at VCC = 5.5 V are equal to the limits at VCC = 4.5 V and guaranteed by testing at VCC = 4.5 V. AC limits at
VCC = 3.6 V are equal to the limits at VCC = 3.0 V and guaranteed by testing at VCC = 3.0 V. Minimum ac limits for
VCC = 5.5 V are 1.0 ns and guaranteed by guardbanding the VCC = 4.5 V minimum limits to 1.5 ns. For propagation delay
tests, all paths must be tested.
TABLE IB. SEP test limits. 1/ 2/
Device
type
01
SEP
No SEL
TC =
temperature
±10°C
+125°C
VCC
Bias VCC = 5.5 V
Effective LET
≤ 93 MeV-cm2/mg
1/ For SEP test conditions, see 4.4.4.2 herein.
2/ Technology characterization and model verification supplemented by in-line data may be used in lieu of end-of-
line testing. Test plan must be approved by TRB and qualifying activity.
STANDARD
MICROCIRCUIT DRAWING
DLA LAND AND MARITIME
COLUMBUS, OHIO 43218-3990
DSCC FORM 2234
APR 97
SIZE
A
REVISION LEVEL
K
5962-87552
SHEET
11